5188238-YIM-D-0518
Johnson Controls Ducted Systems
19
060
(5.0)
208-3-60 16.5
110
25.8
2.8
6.8
0
NONE
-
-
-
30.2
40
E05
4
1
11.1
44.1
50
E07
5.6
1
15.5
49.7
60
E10
8
1
22.2
58
60
E15
11.9
2
33
71.5
80
E20
15.9
2
44.1
85.4
90
E30
22.2
2
61.6
107.3
110
230-3-60 16.5
110
25.8
2.8
6.8
0
NONE
-
-
-
30.2
40
E05
5.3
1
12.7
46.2
50
E07
7.5
1
18
52.8
60
E10
10.6
1
25.5
62.1
70
E15
15.9
2
38.2
78
80
E20
21.2
2
51
94
100
E30
29.6
2
71.2
119.2
125
460-3-60 7.2
52
11.3
2.8
3.15
0
NONE
-
-
-
13.6
20
E07
6.8
1
8.2
23.8
25
E10
10.1
1
12.1
28.7
30
E15
13.6
2
16.4
34
35
E20
19.5
2
23.5
42.9
45
E30
28.8
2
34.6
56.9
60
575-3-60 5.5
38.9
8.6
2.8
2.2
0
NONE
-
-
-
10.2
15
E10
10.6
1
10.2
22.9
25
E15
15.9
2
15.3
29.3
30
E20
21.2
2
20.4
35.7
40
E30
30.4
2
29.3
46.8
50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XN036-060 Without Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps