5188238-YIM-D-0518
Johnson Controls Ducted Systems
25
060
(5.0)
208-3-60 16.5
110
25.8
2.8
6.8
10
NONE
-
-
-
40.2
50
E05
4
1
11.1
54.1
60
E07
5.6
1
15.5
59.7
70
E10
8
1
22.2
68
70
E15
11.9
2
33
81.5
90
E20
15.9
2
44.1
95.4
100
E30
22.2
2
61.6
117.3
125
230-3-60 16.5
110
25.8
2.8
6.8
10
NONE
-
-
-
40.2
50
E05
5.3
1
12.7
56.2
60
E07
7.5
1
18
62.8
70
E10
10.6
1
25.5
72.1
80
E15
15.9
2
38.2
88
90
E20
21.2
2
51
104
110
E30
29.6
2
71.2
129.2
150
460-3-60 7.2
52
11.3
2.8
3.15
5
NONE
-
-
-
18.5
25
E07
6.8
1
8.2
28.8
30
E10
10.1
1
12.1
33.7
35
E15
13.6
2
16.4
39
40
E20
19.5
2
23.5
47.9
50
E30
28.8
2
34.6
61.9
70
575-3-60 5.5
38.9
8.6
2.8
2.2
4
NONE
-
-
-
14.2
15
E10
10.6
1
10.2
26.9
30
E15
15.9
2
15.3
33.3
35
E20
21.2
2
20.4
39.7
40
E30
30.4
2
29.3
50.8
60
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XN036-060 With Powered Convenience Outlet (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps