background image

PAGE 13

MAXA-MI$ER

Ô

UNITARY ENERGY RECOVERY VENTILATOR

MODEL VR028A15M/H & VR028A25H  (STATIONARY) 

 INSTALLATION

INSTRUCTIONS

5257527-UAI-A-0616 / R28A-18YSDW

In order for the ERV to operate with maximum
effectiveness the Smart Equipment Control (SEC) must
have the latest 3.1 (or greater) firmware installed. In order
to determine the version of firmware present within the
control follow the menu steps below.

Status> Scroll down to "Update"> Enter> View Version

If a firmware update is required be sure to perform a
backup of the units factory settings if updating the
firmware. The procedure below outlines the backup and
restore functions of the SE units control board. Once the
procedures outlined in the document, the following set
points will have been changed to the status shown below.

I - Set Points

Set Points

Sta tus

BACOid

Economizer En able

ON

29747

Power Ex haust En able

ON

29787

Non-Mod u lat ing  Power  Ex haust

ON

29503

These settings can be accessed within the RTU- SE UCB
menu.  Please refer to the RTU's SE "

Quick Start

" guide

for menu navigation using the onboard LCD display,
joystick and enter/cancel buttons. 

Please see the

following pages for instructions on how to navigate
the Smart Control (SE) menus and setting up the
control to operate with an ERV.

II - SE Procedures to Backup / Restore

1.

Once the packaged unit is powered up the 120 second
startup delay begins. Once the delay expires there
may or may not be a "

Start Up

" delay displayed. To

cancel the second time delay press the "

Cancel

"

button for six seconds. 

See Figure 1.

Startup

Figure 1

Update

Figure 2

Backup

Figure 3

2.

Once the control is out of time delay mode, press the
Joystick down through the following menus: 

Status>

Alarms> Summary> Commission> Controller>
Update, Push ENTER

 (

See Figure 2

)

3.

Once the screen and cursor are on "

Update

".

Press 

Enter 

and scroll through the menus until the

screen and cursor displays "

Backup

". If an USB flash

drive is present or is inserted into the on board USB
port, pressing enter when "

Backup

" is displayed the

backup will begin sending factory defaults and other
settings to the USB flash drive. 

See Figure 3.

4.

Once the backup is performed (Screen shows BCFG
100%) the 3.1 or greater version of the controls
firmware can be loaded. Please see the details on the
following pages on how to perform the firmware
updates.

III– SE Procedures to Update 

Updating the program in the SE control by USB if
required.

WARNING! 

In order for the ERV to properly operate with

the SE control version 3.1.0.0.0128 or greater must be
installed. Load the appropriate files to a clean USB Flash
Drive as indicated in the prior five steps. 

(Files located on UPGNET>UST and Technical
Services Center>Tech Services Software Updates)

Содержание VR028A15H

Страница 1: ...ontact with sharp edges WARNING Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies MAXA MI ERÔ UNITARY ENERGY RECOVERY VENTILATOR MODEL VR028A15M H VR028A25H STATIONARY INSTALLATION INSTRUCTIONS 5257527 UAI A 0616 R28A 18YSDW ETL Certified per UL ...

Страница 2: ... damper frame within reach of field wiring harness See Figure 7 9 Connect the communication wire and power wire located in the accessory wiring bundle in the RTU return air section to the proper terminals on the economizer control board See SSE field harness diagram at the back of this manual See Figure 8 10 Route the provided field wiring harness through the balancing damper into the return air s...

Страница 3: ...as the legs will have to be adjusted once the unit is finally set in place 14 Locate provided roll of x 1 gasket material Apply gasket down the center post of the UERV as well as between the platform support rail and adaptor panel 15 Remove screw from the top panel of the RTU in order to enable lifting the top panel of the RTU up at least 2 Note An equipment support or pressure treated 2x6x60 piec...

Страница 4: ...transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85 of the difference in total energy contained within the two air streams Sensible and latent heat are the two components of total heat Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air The latent heat load from the o...

Страница 5: ...hould be removed Also if system check out is being conducted at low ambient temperatures technician should be aware that this kit can cause system not to operate 4 Verify that the UERV 3 three phase blower motors are phased sequentially ensuring correct rotation and operation a Disconnect power b Reverse any two field power leads to the UERV c Reapply power MAXA MI ERÔ UNITARY ENERGY RECOVERY VENT...

Страница 6: ... rear and unplug J150 and P150 Refer to wiring diagrams in this instruction manual Remove segment and wash with water and or mild detergent To install wheel segments follow steps A through E See Figure 15 Reverse procedure for segment removal A Unlock two segment retainers one on each side of the selected segment opening B With the embedded stiffener facing the motor side insert the nose of the se...

Страница 7: ...P models L5 LAK SSJ not used on P models L6 LAK SSJ PS not used on P models L7 LAK PS L8 LAK MOA and PS M1 Motorized Outside Air MOA M2 MOA SSJ not used on P models M3 MOA SSJ PS PS not used on P models M4 MOA PS S1 Stop Start Job SSJ not used on P models S2 SSJ PS not used on P models P1 Pressure Sensor PS Voltage 2 208 230v 3ph 4 460v 3ph 5 575v 3ph 9 208 320v 1ph Duct Type A No Selection on Roo...

Страница 8: ...1 04 1 09 1 09 1 09 1 08 1 05 0 99 0 90 0 82 0 75 0 89 0 88 0 87 0 85 0 81 0 75 0 66 0 59 0 5 0 69 0 68 0 65 0 62 0 57 0 5 0 42 0 35 0 25 0 00 0 20 0 40 0 60 0 80 1 00 1 20 1 40 1500 1600 1700 1800 2000 2200 2400 2600 2800 SCFM Equation of line SCFM PD 0 01 0 00036 TABLE 1 PRESSURE DROP in of W C R28 Series 1100 RPM 1000 RPM 900 RPM 800 RPM ...

Страница 9: ...PAGE 9 ...

Страница 10: ...r Harness J151 Jack Exhaust Air Motor Harness P153 Plug Field Harness P160 Plug Damper Intake Motor Harness P161 Plug Damper Exhaust Motor Harness RS 1 Rotation Sensor Optional S26 Switch Low Ambient Optional S51 Switch Door S52 Switch Damper Intake S53 Switch Damper Exhaust SD Smoke Detector Optional SSJ Climate Smart Board Optional T27 Transformer Control T28 Transformer Step down Optional TB37 ...

Страница 11: ... n u r e p o r p r o f l a n i m r e t e g a t l o v e v i t c e l e S 4 h c t i w s t n e i b m a w o l l a n o i t p O 5 r e p m a d e k a t n i d e z i r o t o m l a n o i t p O 6 t r a m S e t a m i l C l o r t n o c g o j d n a t r a t s p o t s l a n o i t p O 7 t i n u p o t f o o r h t i w t c e n n o c o t d e d i v o r p s s e n r a h r e t p a d a g n i h c t a M 8 r e p m a d t s u a h...

Страница 12: ...PAGE 12 EQUIPMENT LAYOUT ...

Страница 13: ...h an ERV II SE Procedures to Backup Restore 1 Once the packaged unit is powered up the 120 second startup delay begins Once the delay expires there may or may not be a Start Up delay displayed To cancel the second time delay press the Cancel button for six seconds See Figure 1 Startup Figure 1 Update Figure 2 Backup Figure 3 2 Once the control is out of time delay mode press the Joystick down thro...

Страница 14: ...ed past you return by pressing the joy stick lever up until the Update screen appears Screen will read Contrler Controller Update Enter Cancel Buttons Figure 6 View Ver Figure 7 LoadFirm Figure 8 Confirm Figure 9 USB OK Figure 4 4 Press ENTER Screen will read View Ver Version Load Firm Backup 5 Toggle Joy stick down so the arrow is next to Load Firm 6 Press ENTER Screen shows software versions pre...

Страница 15: ...E unit control 1 Scroll through menus by pressing down on joystick Status Alarms Summary Commission Econ Economizer Enable Make sure this is set to Yes ERV En Figure 11 Econ En Figure 10 2 Scroll through menus by pressing down on joystick Status Alarms Summary Commission PowerEx ERV Enable Make sure this is set to Yes 3 The economizer minimum setting must be set at 50 or greater Status Alarms Summ...

Страница 16: ...actor Start Up Mechanic q Inspect the unit for transit damage and report any damage on the carrier s freight bill q Check model number to insure it matches the job requirements q Install field accessories and unit adapter panels as required Follow accessory and unit installation manuals q Verify field wiring including the wiring to any accessories q Check all multi tap transformers to insure they ...

Отзывы: