103904-UIM-B-0505
10
Unitary Products Group
TABLE 9: Electrical Data (for Multi-source Power Supply) - Copper Wire 208/230-1-60
1
N1VS
Model
Heater
Model
Min. Circuit Ampacity
Max. O.C.P.
2
Amps/Type
75°C Wire Size - AWG
Circuit
Circuit
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
B1206
2HK16501506B 29.1/31.4 45.1/52.1
-
30/35
50/60
-
10/8
8/6
-
2HK16501806B 29.1/31.4 28.2/32.6 28.0/32.6 30/35
30/35
30/35
10/8
10/8
10/8
2HK16501906B 40.5/44.4 45.7/52.6
-
45/45
50/60
-
8/8
8/6
-
D1206
2HK16501506B 29.1/31.4 45.1/52.1
-
30/35
50/60
-
10/8
8/6
-
2HK16501806B 29.1/31.4 28.2/32.6 28.0/32.6 30/35
30/35
30/35
10/8
10/8
10/8
2HK16501906C 40.5/44.4 45.7/52.6
-
45/45
50/60
-
8/8
8/6
-
C1606
2HK16501506B 30.7/32.9 45.1/52.1
-
35/35
50/60
-
8/8
8/6
-
2HK16502006B 52.9/59.0 45.1/52.1
-
60/60
50/60
-
6/6
8/6
-
D2006
2HK16501506B 33.0/34.8 45.1/52.1
-
35/35
50/60
-
8/8
8/6
-
2HK16502006B 55.2/60.8 45.1/52.1
-
60/70
50/60
-
6/4
8/6
-
2HK16502506B 33.0/34.8 45.1/52.1 45.1/52.1 35/35
50/60
50/60
8/8
8/6
8/6
2HK16503006A 55.2/60.8 45.1/52.1 45.1/52.1 60/70
50/60
50/60
6/4
8/6
8/6
1.
Heat amps shown at 240V represents maximum heater rating.
2.
OCP = Over current protection, HACR type circuit breaker or time delay fuse.
TABLE 10: Electrical Data (for Multi-source Power Supply) - Copper Wire 208/230-3-60
1
N1VS Model
Heater Model
Min. Circuit Ampacity
Max. O.C.P.
2
Amps/Type
75°C Wire Size - AWG
Circuit
Circuit
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
208/240V
D2006
2HK16503025A
48.1/52.9
39.1/45.1
-
50/60
40/50
-
8/6
8/8
-
1.
Heat amps shown at 240V represents maximum heater rating.
2.
OCP = Over current protection, HACR type circuit breaker or time delay fuse.
TABLE 11: Electrical Data - Cooling Only (60 Hz)
Model N1VS
Minimum Circuit Ampacity
Maximum
O.C.P.D.
Minimum Wire
Size A.W.G.
60 Hz
208V
230V
B1206 5.9
5.4 15
14
D1206 5.9
5.4 15
14
C1606 7.6
6.9 15
14
D20-6 9.7
8.8 15
14