![York International N Series Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/york-international/n-series/n-series_installation-manual_913858008.webp)
103904-UIM-B-0505
8
Unitary Products Group
*
May be 0 (no breaker) or 1 (with breaker).
**
If first stage heat or 66 is connected to W1, otherwise refer to this table.
**
If first stage heat or 66 is connected to W1, otherwise refer to this table.
*
May be 0 (no breaker) or 1 (with breaker).
TABLE 5: Electrical Data - 208/230-1-60
1
N1VS
Model
Heater
Model*
Min. CFM &
Max. Static
Fan
FLA
240
Total Heat
2
KW Staging**
KW
MBH
W1 Only
W2 Only
W1 + W2
Static
Tap
208
240
208
240
208
240
208
240
208
240
B1206
2HK*6500506B
0.5 715 4.3
3.8 5.0 13.0
17.1 3.8 5.0 3.8 5.0 3.8 5.0
2HK*6500806B
5.6 7.5 19.1
25.6 3.8 5.0 5.6 7.5 5.6 7.5
2HK*6501006B
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK16501506B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK16501806B
13.2 17.6 45.1 60.1 3.8 5.0 8.5 11.3 13.2 17.6
2HK16501906B
13.2 17.6 45.1 60.1 2.8 3.8 10.4 13.8 13.2 17.6
D1206
2HK*6500506C
0.5 715 4.3
3.8 5.0 13.0
17.1 3.8 5.0 3.8 5.0 3.8 5.0
2HK*6500806B
5.6 7.5 19.1
25.6 3.8 5.0 5.6 7.5 5.6 7.5
2HK*6501006B
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK16501506B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK16501906C
13.2 17.6 45.1 60.1 2.8 3.8 10.4 13.8 13.2 17.6
C1606
2HK*6500506B
0.5 1110 5.5
3.8 5.0 13.0
17.1 3.8 5.0 3.8 5.0 3.8 5.0
2HK*6500806B
5.6 7.5 19.1
25.6 3.8 5.0 5.6 7.5 5.6 7.5
2HK*6501006B
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK16501506B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK16502006B
15.0 20.0 51.2 68.3 3.8 5.0 7.5 10.0 15.0 20.0
D2006
2HK*6500806B
0.5 1335 7.0
5.6 7.5 19.1
25.6 3.8 5.0 5.6 7.5 5.6 7.5
2HK*6501006B
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK16501506B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK16502006B
15.0 20.0 51.2 68.3 3.8 5.0 7.5 10.0 15.0 20.0
2HK16502506B
18.8 25.0 64.2 85.3 3.8 5.0 11.3 15.0 18.8 25.0
2HK16503006A
22.5 30.0 76.8 102.4 7.5 10.0 15.0 20.0 22.5 30.0
1.
Heat KW shown at 240V represents maximum heater rating. See conversion table above for voltage multiplier.
2.
See conversion table above.
TABLE 6: Electrical Data - 208/230-3-60
1
N1VS Model
Heater
Model*
Min. CFM &
Fan
FLA
240
Total Heat
1
KW Staging**
Max. Static
KW
MBH
W1 Only
W2 Only
W1 + W2
Static
Tap
208
240
208
240
208
240
208
240
208
240
B1206
2HK06501025B
0.5 715 4.3
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK06501525B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK06501825B
13.2 17.6 45.1 60.1 3.8 5.0 8.5 11.3 13.2 17.6
D1206
2HK06501025B
0.5 715 4.3
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK06501525B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK06501825B
13.2 17.6 45.1 60.1 3.8 5.0 8.5 11.3 13.2 17.6
C1606
2HK06501025B
0.5 1110 5.5
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK06501525B
11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK06501825B
13.2 17.6 45.1 60.1 3.8 5.0 8.5 11.3 13.2 17.6
D2006
2HK06501025B
0.5 1335 7.0
7.5 10.0 25.6 34.1 3.8 5.0 7.5 10.0 7.5 10.0
2HK06501525B
11.3 15.0 38.8 51.2 3.8 5.0 7.5 10.0 11.3 15.0
2HK06501825B
13.2 17.6 45.1 60.1 3.8 5.0 8.5 11.3 13.2 17.5
2HK16503025A
22.5 30.0 76.8 102.4 7.5 10.0 15.0 20.0 22.5 30.0
1.
Heat KW shown at 240V represents maximum heater rating. See conversion table above for voltage multiplier.