York International N Series Скачать руководство пользователя страница 6

103904-UIM-B-0505

6

Unitary Products Group

NOTE: All wiring must comply with local and national electrical code

requirements. Read and heed all unit caution labels.

NOTE: It is possible to vary the amount of electric heat turned on during

the defrost cycle of a heat pump. Standard wiring will only bring
on 5 - 10 KW of electric heat during defrost, depending on the
size of the heater.

LINE POWER CONNECTIONS

Power may be brought into the unit through the supply air end of the
unit (top when unit is vertical) or the left side panel. Use the hole appro-
priate to the unit’s orientation in each installation to bring conduit from
the disconnect. The power lead conduit should be terminated at the
electrical control box. Refer to Tables 6, 7, 8 for wire requirements. Also
see Figure 11.

BLOWER SPEED COMFORT SELECTION

NOTE: 

1.

Both the "COOL" and the "ADJ" tap must be set for the cooling CFM.

2.

Fan only CFM = 63% of high speed cooling.

3.

Low speed cooling used only with two stage outdoor units. (Speed is preset
to 65% of high speed).

4.

Dehumidification speed is 85% of cooling speed.

5.

When operating in both heat pump and electric heat modes, the CFM will be
whichever is greater.

6.

CFM indicator light flashes once for every 100 CFM. (i.e.: 12 Flashes is
1200 CFM)

These variable speed air handlers are designed to deliver constant
CFM regardless of the external static pressure (ESP) in the ductwork.
Therefore, if too many supply registers are closed, a filter becomes
clogged, or there is a restriction in the ductwork, the motor will automat-
ically operate at a higher speed to compensate for the higher ESP. This
may result in a higher operating sound level.

All CFM’s are shown at 0.5” w.c. external static pressure. These units
have variable speed motors that automatically adjust to provide con-
stant CFM from 0.0” to 0.6” w.c. static pressure. From 0.6” to 1.0” static
pressure, CFM is reduced by 2% per 0.1” increase in static. Operation
on duct systems with greater than 1.0” w.c. external static pressure is
not recommended.

To Set Cooling CFM:

Refer to the outdoor unit technical guide for the recommended airflow
with the matching evaporator coil. Refer to the label in the bag attached
to the blower housing or Table 2 for the possible high speed cooling and
heat pump CFM selections.

Find the recommended system airflow in the Table for the installed Air
Handler model.

Select the "COOL" CFM you need from Table 2. Set "COOL" and "ADJ"
Jumpers on the CFM selection board as indicated in Table 2.

To Set Heat Pump CFM:

The heat pump CFM setting is the same as the cooling CFM. No addi-
tional CFM setting is required, however, you must remove the jumper at
the bottom of the connector board labeled "Remove for Heat Pump" for
heat pump operation (See Figure 8).

To Set Electric Heat CFM:

The blower speed required for the Electric Heat is different than cooling.
Refer to the label in the bag attached to the blower housing or Table 2
for the possible CFM selections. Refer to Tables 5 or 6 for the minimum
required CFM for the electric heater installed. Find the desired airflow in
Table 2. Set the "Heat" Jumper on the CFM selection board to tap
shown.

To Set Delay Profile:

Every variable speed air handler has multiple "blower off delay" profiles
to optimize system performance and efficiency. Refer to Table 2 or the
instructions in the bag attached to the blower housing for the type of
system installed. Set the "DELAY" jumper tap position horizontally on
the CFM selection board for the appropriate setting.

Fan Only CFM:

When the connection is made from "R" to "G", the fan only mode is acti-
vated. In this mode, the blower will deliver 63% of the cooling system
CFM. This connection is factory set from the manufacturer and cannot
be field adjusted.

To Install Humidistat Accessory:

If the system is used with a humidistat accessory, connect the field
wires to screw terminals "R" and "Hum" on the CFM selection board
(See Figures 12, 13, 14, 15, 16, 17, 18, 19, and 20).

IMPORTANT: Remove the jumper at the bottom of the connector board
marked "Remove for Humidistat" for humidistat operation.

TABLE 2: CFM / Comfort Tap Selection

HIGH SPEED COOLING AND HEAT PUMP CFM 

MODEL JUMPER 

SETTING

N1VSB12 N1VSD12 N1VSC16 N1VSD20 

"COOL 

TAP" 

"ADJ 
TAP" 

1250 1400

1650 2100  "A"  "B" 

1230 1230

1570 1980  "B"  "B" 

1150 1220

1500 1860  "A"  "A" 

1070 1070

1425 1750  "B"  "A" 

1035 1100

1350 1675  "A"  "C" 

1000 1000

1305 1605  "C"  "B" 

965 965

1285 

1575 "B"  "C" 

820 820

1220 

1510 "D"  "B" 

870 870

1185 

1420 "C"  "A" 

715 715

1110 

1335 "D"  "A" 

785 785

1065 

1280 "C"  "C" 

645 645

1000 

1200 "D"  "C" 

COMFORT SETTING 

"DELAY" TAP 

UNIT TYPE 

Jumper at "A" 

Normal Profile 

Jumper at "B" 

Humid Profile

Jumper at "C" 

Dry Profile

Jumper at "D" 

Temperate Profile

ELECTRIC HEAT CFM 

MODEL

TAP

SELECTIONS

N1VSB12

N1VSD12

N1VSC16

N1VSD20

"HEAT"

1150 1220

1500 

1860  "A" 

1070 1070

1425 

1750  "B" 

870 870

1185 

1420 "C" 

715 715

1110 

1335 "D" 

 FIGURE 8:  CFM Selection Board Detail

DO NOT change the "ADJ" tap position on the CFM selection board
as this will change your cooling CFM previously selected.

CFM SELECTION BOARD

TAP SELECTION

D
C
B
A

D
C
B
A

COOL

HEAT

ADJ

DELAY

REMOVE FOR

HEAT PUMP

HUMIDISTAT

Содержание N Series

Страница 1: ...ANCES 2 LOCATION 2 DUCT CONNECTIONS 4 SUSPENSION KITS 4 INDOOR UNIT PREPARATION 5 BLOWER COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS 5 BLOWER COIL ASSEMBLY DOWNFLOW INSTALLATION 5 ELECTRIC HEATERS OPERATING CONTROLS 5 LOW VOLTAGE CONTROL CONNECTIONS 5 LINE POWER CONNECTIONS 6 BLOWER SPEED COMFORT SELECTION 6 WIRING DIAGRAMS 11 DRAIN CONNECTIONS 14 MAINTENANCE 14 COIL CLEANING 14 LUBRICATION ...

Страница 2: ...ructions are required as a minimum for a safe installation GENERAL INFORMATION This Modular Air Handler provides the flexibility for installation in any upflow downflow or horizontal application These versatile models may be used with or without electric heat The variable speed ECM motors provide a selection of air volume to match any application The unit can be positioned for bottom return air in...

Страница 3: ...en into consideration and provided for as follows a Refrigerant piping and connections are located in the front b Maintenance and servicing through the front or access side of unit with both sides and rear of unit having zero inch clear ance c Condensate drain lines are connected in the front clear of fil ter d Filter removal e When no electric heat is used the unit as well as all duct work and pl...

Страница 4: ...charge opening sizes shown in Figure 4 Duct work should be fabricated and installed in accordance with local and or national codes This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilat ing Systems NFPA No 90B SUSPENSION KITS A suspension kit is available Models 1BH0601 is designed specifically for the units contained in this instr...

Страница 5: ...sly See Figure 10 Mark the unit nameplate with the appropriate heater selection on the space provided or NONE to indicate cooling only To operate these units with electric heat it is necessary to field install an electric heater kit 2HK See Electric Heater Accessory Installation instructions for proper installation procedure Prior to installing electric heat it is necessary to perform the followin...

Страница 6: ...umpers on the CFM selection board as indicated in Table 2 To Set Heat Pump CFM The heat pump CFM setting is the same as the cooling CFM No addi tional CFM setting is required however you must remove the jumper at the bottom of the connector board labeled Remove for Heat Pump for heat pump operation See Figure 8 To Set Electric Heat CFM The blower speed required for the Electric Heat is different t...

Страница 7: ...SINGLE SOURCE 2 5 25 KW 25 KW SHOWN 1 PHASE ELECTRIC HEAT WITH CIRCUIT BREAKER BREAKER BAR REMOVED MULTI SOURCE 15 25 KW 25 KW SHOWN TYPICAL WIRING WITHOUT ELECTRIC HEAT GND LUG POWER SUPPLY GND LUG GND LUG POWER SUPPLY GND LUG GND LUG POWER SUPPLY 1 GND LUG GND LUG POWER SUPPLY GND LUG POWER SUPPLY 2 POWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUC...

Страница 8: ...K 6500806B 0 5 1335 7 0 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 2HK16502006B 15 0 20 0 51 2 68 3 3 8 5 0 7 5 10 0 15 0 20 0 2HK16502506B 18 8 25 0 64 2 85 3 3 8 5 0 11 3 15 0 18 8 25 0 2HK16503006A 22 5 30 0 76 8 102 4 7 5 10 0 15 0 20 0 22 5 30 0 1 Heat KW shown at 240V represen...

Страница 9: ...55 2 60 8 60 70 6 4 2HK16501506B 62 5 78 0 86 9 80 90 4 3 2HK16502006B 83 3 100 3 112 9 110 125 2 1 2HK16502506B 104 2 123 1 139 0 125 150 1 1 0 2HK16503006A 125 0 145 3 165 0 150 175 1 0 2 0 1 Heat amps shown at 240V represents maximum heater rating 2 OCP Over current protection HACR type circuit breaker or time delay fuse TABLE 8 Electrical Data for Single Source Power Supply Copper Wire 208 230...

Страница 10: ... 52 1 35 35 50 60 8 8 8 6 2HK16502006B 55 2 60 8 45 1 52 1 60 70 50 60 6 4 8 6 2HK16502506B 33 0 34 8 45 1 52 1 45 1 52 1 35 35 50 60 50 60 8 8 8 6 8 6 2HK16503006A 55 2 60 8 45 1 52 1 45 1 52 1 60 70 50 60 50 60 6 4 8 6 8 6 1 Heat amps shown at 240V represents maximum heater rating 2 OCP Over current protection HACR type circuit breaker or time delay fuse TABLE 10 Electrical Data for Multi source...

Страница 11: ...y for SEER enhancement 1 Optional Dehumidification Humidistat contacts open on rise Remove Humidistat Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application For Heat Pump Applications Remove Heat Pump Jumper on CFM selection board Refer to CFM Selection Board Graphic To change quantity of heat during HP defrost cycle Rev...

Страница 12: ...t Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application Y Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 Second Blower Off Delay for SEER enhancement 1 Optional Dehumidification Humidistat contacts open on rise Remove Humidistat Jumper on CFM selection board Refer to C...

Страница 13: ...Humidistat Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application For Heat Pump Applications Remove Heat Pump Jumper on CFM selection board Refer to CFM Selection Board Graphic To change quantity of heat during HP defrost cycle Reverse connections at W1 W2 on Air Handler Control Board FIGURE 20 Control Wiring N1VS New UP...

Страница 14: ...to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur faces LUBRICATION The bearings of the blower motor are permanently lubricated CONDENSATE DRAINS During the cooling season check the condens...

Страница 15: ...103904 UIM B 0505 Unitary Products Group 15 NOTES ...

Страница 16: ...to change without notice Printed in U S A 103904 UIM B 0505 Copyright by York International Corp 2005 All rights reserved Supersedes 103904 UIM A 1204 Unitary 5005 Norman Product York OK Group Drive 73069 NOTES ...

Отзывы: