<5. List of Parameters>
5-5
IM 01C50T03-02EN
No.
Name
Description
RW
Remarks
Default
Upload/
download
parameter
I40
NRML MIN
OUT
Setting of operation output lower
limit
RW 3.60 to 4.00 mA
3.68 mA
I41
NRML MAX
OUT
Setting of operation output upper
limit
RW 20.00 to 21.60 mA
20.8 mA
I60
SELF CHECK Self-diagnosis
R
Same as A60
―
J
LCD DISPLAY
Indicator
J10
D INFO PARM Display setting of DISP1/2 process
variable name
RW OFF
ON
ON
J11
D INFO UNIT
Display setting of DISP1/2 unit
RW OFF
ON
ON
J12
D INFO
STYPE
Display setting of DISP1/2 sensor
type
RW OFF
ON
OFF
J13
D INFO
SWIRE
Display setting of DISP1/2 sensor
connection wires
RW OFF
ON
OFF
J20
DISP1 VRBL
DISP1 display - Process variable
selection
RW PV
SV
TV
QV
PV
J21
DISP1 POINT DISP1 - Decimal point position
setting
RW
0
1
2
3
1
J22
DISP2 VRBL
DISP2 display - Process variable
selection
RW PV
SV
TV
QV
Not used
Not used
J23
DISP2 POINT DISP2 - Decimal point position
setting
RW
0
1
2
3
1
J30
% DISPLAY
% output display setting
RW OFF
ON
OFF
J31
% POINT
% output - Decimal point position
setting
RW
0
1
2
3
1
J32
mA DISPLAY
Current output - Display setting
RW OFF
ON
OFF
J33
mA POINT
Current output - Decimal point
position setting
RW
0
1
2
3
2
J40
BAR GRAPH
Bar graph display setting
RW OFF
ON
ON
J50
DISP CYCLE
Display cycle setting
RW HIGH
MID
LOW
MID
J60
SELF CHECK Self-diagnosis
R
Same as A60
―
K
ALARM
MASK
Alarm Mask
K10
S1 FAIL MASK Mask setting for S1 Failure alarm
*3
RW NO MASK
MASK
NO MASK
K11
*1
S2 FAIL MASK Mask setting for S2 Failure alarm
*3
RW NO MASK
MASK
NO MASK
K12
S1 SHRT
MASK
Mask setting for S1 Short alarm *3 RW NO MASK
MASK
MASK
K13
*1
S2 SHRT
MASK
Mask setting for S2 Short alarm *3 RW NO MASK
MASK
MASK