<3. Parameter Setting>
3-11
IM 01C50T03-02EN
3.2.10 Integral Indicator Display Mode
If the temperature transmitter has an integral
indicator, you can set the display items and the
updating cycle.
F0307.ai
P
SP
T
F
%
(1) Setting the display items
The integral indicator can display up to four
channels (Disp Out1, Disp Out2, Disp %, and Disp
mA, except for alarm indication).
Of these, Disp % is “% of RANGE”, and Disp mA
is a dedicated channel of “mA of RANGE”. As the
display content is fixed, you can only specify ON or
OFF.
Any process variables PV to QV can be specified
for “Disp Out1” and “Disp Out2”. One of the process
variables must always be specified for the “Disp
Out1” channel. The “Disp Out2” channel can be set
not to display by setting it to “Not Used”.
Table 3.1 shows process variables that can be
specified for each display channel.
Display
channel
Process variable
Disp
Out1
Disp
Out2
Disp
%
Disp
mA
PV
✓
✓
SV
✓
✓
TV
✓
✓
QV
✓
✓
mA of RANGE
✓
% of RANGE
✓
The following shows the setting parameters of each
display channel.
Display
channel
Variable
selection
Remarks
Disp Out1
J20:DISP1 VRBL Select from PV to
QV.
Disp Out2
J22:DISP2 VRBL Select from PV to
QV, or “Not Used”.
Disp %
J30:% DISPLAY Select from ON or
OFF.
Disp mA
J32:mA DISPLAY Select from ON or
OFF.
(2) Selecting the decimal-point position
You can specify the position of the decimal point
(the number of digits displayed after the decimal
point) for each display channel.
Specify the number of display digits (an integer from
0 to 3) after the decimal point.
Display channel
Decimal-point position
Disp Out1
J21:DISP1 POINT
Disp Out2
J23:DISP2 POINT
Disp %
J31:% POINT
Disp mA
J33:mA POINT
(3) Setting the display cycle
Set the display switching cycle. When the time
corresponding to the preset display cycle has
elapsed, the following information is displayed.
Set the cycle using the “J50:DISP CYCLE”
parameter. Select the “HIGH”, “MID”, or “LOW”
cycle.
Selection value
Display switching cycle
HIGH
1200 ms
MID
2400 ms
LOW
3600 ms
(4) Setting the display information
When the numerical information of each display
channel is displayed on the upper part of the display
meter, the information attached to the process
variable can be displayed in the lower row.
To display the incidental information, turn the
display ON or OFF using the following parameters.
This setting is valid for all display channels.
Setting parameter
Incidental information
J10:D INFO PARM
Process variable name
J11:D INFO UNIT
Unit of process variable
J12:D INFO STYPE
Sensor type
J13:D INFO SWIRE
Number of sensor wire
connections