<5. List of Parameters>
5-4
IM 01C50T03-02EN
No.
Name
Description
RW
Remarks
Default
Upload/
download
parameter
H30 TERM LSL
Lower limit temperature of terminal
sensor measuring range
R
-200.0 degC
H31 TERM USL
Upper limit temperature of terminal
sensor measuring range
R
+850.0 degC
H32 TERM MIN
SPN
Terminal sensor minimum span
R
10.0 degC
H60 SELF CHECK Self-diagnosis
R
Same as A60
―
I
ADJUST
Adjustment
I10
S1 2W
RESIST
Resistance for Sensor1 RTD
2-wire correction
(Cable resistance)
RW
0.000 ohms
I11
SENSOR1
Sensor1 output value
R
Same as D12
―
I12
S1 ZERO ADJ Sensor1 zero adjustment value
RW Adjustment point
0.0 degC
I13
S1 SPAN ADJ Sensor1 span adjustment value
RW Adjustment point
100.0 degC
I14
S1 ZERO DEV Sensor1 zero adjustment amount
R
Difference between
the adjustment point
and the unadjusted
measured value
0.0 degC
I15
S1 SPAN DEV Sensor1 span adjustment amount
R
Difference between
the adjustment point
and the unadjusted
measured value
0.0 degC
I16
S1 ADJ CLR
Clear of Sensor1 adjustment data
RW NO EXEC
EXEC
NO EXEC
I17
S1 SERIAL NO Sensor1 serial number
RW Sixteen alphanumeric
characters
Sixteen blank
characters
I20
*1
S2 2W
RESIST
Resistance for Sensor2 RTD
2-wire correction
(Cable resistance)
RW
0.000 ohms
I21
*1
SENSOR2
Sensor2 output value
R
Same as D32
―
I22
*1
S2 ZERO ADJ Sensor2 zero adjustment value
RW Adjustment point
0.0
I23
*1
S2 SPAN ADJ Sensor2 span adjustment value
RW Adjustment point
100.0
I24
*1
S2 ZERO DEV Sensor2 zero adjustment amount
R
Difference between
the adjustment point
and the unadjusted
measured value
0.0
I25
*1
S2 SPAN DEV Sensor2 span adjustment amount
R
Difference between
the adjustment point
and the unadjusted
measured value
0.0
I26
*1
S2 ADJ CLR
Clear of Sensor2 adjustment data
RW NO EXEC
EXEC
NO EXEC
I27
*1
S2 SERIAL NO Sensor2 serial number
RW Sixteen alphanumeric
characters
Sixteen blank
characters
I30
OUTPUT
Output setting for user output
adjustment
RW NORMAL
4 mA
20 mA
NORMAL
I31
OUT ZERO
Zero-point setting for user output
adjustment
RW PV value measured by
an external reference
meter during 4 mA
output
4.0 mA
I32
OUT GAIN
Gain point setting for user output
adjustment
RW PV value measured by
an external reference
meter during 20 mA
output
20.0 mA
I33
OUT ADJ CLR Clear of output adjustment data
RW NO EXEC
EXEC
NO EXEC