<5. List of Parameters>
5-1
IM 01C50T03-02EN
5. List of Parameters
Table 5.1
List of Parameters
RW: Display/setting
R: Display only
No.
Name
Description
RW
Remarks
Default
Upload/
download
parameter
01
MODEL
Model
R
YTA710
02
TAG
Tag number
R
Sixteen alphanumeric
characters
Specify during
ordering.
03
SELF CHECK Self-diagnosis
R
GOOD, ERROR
―
A
VARIABLE
Process variable
A10
PV
(Primary variable)
R
Value specified in B10,
and unit specified in
B11
―
A11
mA of RANGE Display of output current
R
―
A12
% of RANGE
Display of output percentage
R
―
A20
SV
Secondary variable
R
Value specified in B20,
and unit specified in
B21
―
A30
TV
Tertiary variable
R
Value specified in B30,
and unit specified in
B31
―
A40
QV
Quaternary variable
R
Value specified in B40,
and unit specified in
B41
―
A50
TERM
Display of terminal block
temperature
R
Unit specified in B51
―
A60
SELF CHECK Self-diagnosis
R
See Table 4.1.
―
B
SET VAR
CON.
Process variable setting of
process variables
B10
PV is
PV mapping
RW See Table 3.2.
Sensor1
B11
PV UNIT
PV unit
RW degC
K
degF
degR
degC
B20
SV is
SV mapping
RW Same as B10
Terminal
B21
SV UNIT
SV unit
RW Same as B11
degC
B30
TV is
TV mapping
RW Same as B10
Terminal
B31
TV UNIT
TV unit
RW Same as B11
degC
B40
QV is
QV mapping
RW Same as B10
Teminal
B41
QV UNIT
QV unit
RW Same as B11
degC
B51
TERM UNIT
Terminal block temperature unit
RW Same as B11
degC
B52
TERM DAMP
Dumping of terminal block
RW 0 to 100 sec
2 sec
B60
SELF CHECK Self-diagnosis
RW Same as A60
―
C
SET TAG
Tag setting
C10
TAG NO.
Tag number
RW Sixteen alphanumeric
characters
―
D
SET INPUT
Input setting
D10 SENSOR1
TYPE
Sensor1 input type
RW See Table 3.1.
Pt100
IEC60751
D11
SENSOR1
WIRE
Sensor1 input wiring
RW 2 WIRE
3 WIRE
4 WIRE
3 WIRE
D12 SENSOR1
Sensor1 output value
R
―
D13 SENSOR1
UNIT
Sensor1 unit selection
RW degC
K
degF
degR
degC