Model YPP6300 Pulse Input Rate/Totalizer
Instruction Manual
14
Modbus
®
RTU Serial Communications
SLAVE ID
1 – 247 (Meter address)
BAUD RATE
300 - 19,200 bps
TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
DATA
8 bit (1 start bit, 1 or 2 stop bits)
PARITY
Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND
DELAY
Less than 2 ms (fixed)
Note: Refer to the
PRO
PLUS
Modbus Register Tables located at
www.yokogawa-usa.com for details.
YPPA1044 Digital Input & Output Expansion Module
CHANNELS
4 digital inputs & 4 digital outputs per module
SYSTEM
Up to 2 modules for a total of 8 inputs & 8 outputs
DIGITAL INPUT
LOGIC HIGH
3 to 5 VDC
DIGITAL INPUT
LOGIC LOW
0 to 1.25 VDC
DIGITAL OUTPUT
LOGIC HIGH
3.1 to 3.3 VDC
DIGITAL OUTPUT
LOGIC LOW
0 to 0.4 VDC
SOURCE
CURRENT
10 mA maximum output current
SINK
CURRENT
1.5 mA minimum input current
+5 V
TERMINAL
To be used as pull-up for digital inputs only.
Connect normally open contacts 5 V & DI 1-4.
Содержание YPP6300
Страница 95: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 95 Figure 21 1 8 DIN Panel Cutout Template...
Страница 96: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 96...
Страница 97: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 97 NOTES...
Страница 98: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 98 NOTES...
Страница 99: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual 99 NOTES...
Страница 100: ...Model YPP6300 Pulse Input Rate Totalizer Instruction Manual LIM6300YK_A SFT039 Ver 2 200 up 11 11...