Communication Commands
:FLICker:MOVe
Function
Moves the observation period number for
measurement of dmax caused by manual
switching.
Syntax
:FLICker:MOVe {<NRf>}
<NRf> = 1 to 24 (observation period number of
destination)
Example
:FLICKER:MOVE 1
Description • The command re-executes measurement if
dmax measurement of certain observation
periods is not made correctly.
• This command can be executed with
measurement of dmax caused by manual
switching (
:FLICker:MEASurement DMAX
).
An error occurs if used during normal flicker
measurement (
:FLICker:MEASurement
FLICker
).
:FLICker:PLT?
Function
Queries all settings related to the long-term flicker
value Plt.
Syntax
:FLICker:PLT?
Example
:FLICKER:PLT? -> :FLICKER:PLT:
STATE 1;LIMIT 0.65;NVALUE 12
:FLICker:PLT:LIMit
Function
Sets the limit of the long-term flicker value Plt or
queries the current setting.
Syntax
:FLICker:PLT:LIMit {<NRf>}
:FLICker:PLT:LIMit?
<NRf> = 0.10 to 99.99 (limit)
Example
:FLICKER:PLT:LIMIT 0.65
:FLICKER:PLT:LIMIT? ->
:FLICKER:PLT:LIMIT 0.65
:FLICker:PLT:NVALue
Function
Sets constant N for the equation used to compute
the long-term flicker value Plt or queries the
current setting.
Syntax
:FLICker:PLT:NVALue {<NRf>}
:FLICker:PLT:NVALue?
<NRf> = 1 to 99 (constant N)
Example
:FLICKER:PLT:NVALUE 12
:FLICKER:PLT:NVALUE? ->
:FLICKER:PLT:NVALUE 12
:FLICker:PLT[:STATe]
Function
Turns ON/OFF judgment of the long-term flicker
value Plt or queries the current setting.
Syntax
:FLICker:PLT[:STATe] {<Boolean>}
:FLICker:PLT:STATe?
Example
:FLICKER:PLT:STATE ON
:FLICKER:PLT:STATE? ->
:FLICKER:PLT:STATE 1
:FLICker:PST?
Function
Queries all settings related to the short-term
flicker value Pst.
Syntax
:FLICker:PST?
Example
:FLICKER:PST? ->
:FLICKER:PST:STATE 1;LIMIT 1.00
:FLICker:PST:LIMit
Function
Sets the limit for the short-term flicker value or
queries the current setting.
Syntax
:FLICker:PST:LIMit {<NRf>}
:FLICker:PST:LIMit?
<NRf> = 0.10 to 99.99 (limit)
Example
:FLICKER:PST:LIMIT 1.00
:FLICKER:PST:LIMIT? ->
:FLICKER:PST:LIMIT 1.00
:FLICker:PST[:STATe]
Function
Turns ON/OFF judgment of the short-term flicker
value Pst or queries the current setting.
Syntax
:FLICker:PST[:STATe] {<Boolean>}
:FLICker:PST:STATe?
Example
:FLICKER:PST:STATE ON
:FLICKER:PST:STATE? ->
:FLICKER:PST:STATE 1
:FLICker:P3D3
Function
Sets the edition of IEC 61000-3-3 or queries the
current setting.
Syntax
:FLICker:P3D3 {<Edition>}
:FLICker:P3D3?
<
Edition> = {ED3P0|ED2P0}
ED3P0:IEC61000-3-3 Ed 3.0
ED2P0:IEC61000-3-3 Ed 2.0
Example
:FLICKER:P3D3 ED3P0
:FLICKER:P3D3 ? ->
:FLICKER:P3D3 ED3P0
:FLICker:P4D15
Function
Sets the edition of IEC 61000-4-15 or queries the
current setting.
Syntax
:FLICker:P4D15 {<Edition>}
:FLICker:P4D15?
<
Edition> = {ED2P0|ED1P1}
ED2P0:IEC61000-4-15 Ed2.0
ED1P1:IEC61000-4-15 Ed1.1
Example
:FLICKER: P4D15 ED2P0
:FLICKER:P4D15 ? ->
:FLICKER:P4D15 ED2P0
Description This is the same setting or query as with the
“
:FLICker:EDITion
” command.
:FLICker:RESet
Function
Resets measured flicker data.
Syntax
:FLICker:RESet
Example
:FLICKER:RESET
6.9 FLICker Group