4.4 Monitoring the Data with PC and FA-M3
This section describes how to monitor measured values from a VZ20X unit
that uses PC and FA
-M3 programming. The sample program reads out
reference numbers 40106 to 40121 continuously.
Modbus function code 03
PC IP: 192.168.1.1
Modbus client
VZ20X
IP: 192.168.1.2
Modbus server
PC
FA-M3
4.4.1 Configuring VZ20X Settings
1. Configure the Ethernet settings.
IP address: 192.168.1.2
Subnet mask: 255.255.255.0
Default gateway: 0.0.0.0
2. Specify the VZ20X [Data acquisition
interval] setting.
In this example, [1 ms] is selected.
Also, select [1-5 V] for [Input type], enter
"5.0000" for [Max. value of input scale],
enter "1.0000" for [Min. value of input
scale], and select [4] for [Input scale
decimal point position].