TI 77V01B01-11EN
Oct.18, 2021-00
4.3.2 Creating the GA10 Modbus Definition File
Use a register in which the
measured values of VZ20X
CH1 to CH8 are continuous.
CH1 measured value -> Channel 0001
CH2 measured value -> Channel 0002
CH3 measured value -> Channel 0003
CH4 measured value -> Channel 0004
CH5 measured value -> Channel 0005
CH6 measured value -> Channel 0006
CH7 measured value -> Channel 0007
CH8 measured value -> Channel 0008
Register number
(Reference no.)
Hex number
(hexadecimal)
Register name
R/W
Descriptions
40101
0064
Measured value time stamp
R
The time of measured values
can be read.
This setting is common to all
channels.
The coordinated universal time
or UTC can be read as a 64 -bit
unsigned integer.
40102
0065
R
40103
0066
R
40104
0067
R
40105
0068
Device status
R
The device status of the VZ20X
can be read.
40106
0069
CH1 measured value
R
Measured values can be read
as 32-bit signed integers.
The range changes depending
on the input range.
40107
006A
R
40108
006B
CH2 measured value
R
40109
006C
R
40110
006D
CH3 measured value
R
40111
006E
R
40112
0
06F
CH4 measured value
R
40113
0070
R
40114
0071
CH5 measured value
R
40115
0072
R
40116
0073
CH6 measured value
R
40117
0074
R
40118
0075
CH7 measured value
R
40119
0076
R
40120
0077
CH8 measured value
R
40121
0078
R
40122
0079
CH1 measured value status
R
The status of measured values
can be read.
40123
007A
CH2 measured value status
R
40124
007B
CH3 measured value status
R
40125
007C
CH4 measured value status
R
40126
007D
CH5 measured value status
R
40127
007E
CH6 measured value status
R
40128
0
07F
CH7 measured value status
R
40129
0080
CH8 measured value status
R
4.3.2 Creating the GA10 Modbus Definition File
The file output path is as follows:
C:¥
Program Files
¥
Yokogawa Electric Corporation
¥S Data Logging Software¥Modbus
2. Save the GA10 Modbus definition file.
Click for the Modbus definition file, then enter a name and save it.
3. Output the GA10 Modbus definition file.
Click for the created Modbus definition file to output it.
"VZ20X_8CH" is used here as an example.
46