4.2.1 Configuring VZ20X Settings
1. Configure the Ethernet settings.
IP address: 192.168.1.2
Subnet mask: 255.255.255.0
Default gateway: 0.0.0.0
2. Although the fastest communication
interval setting for the GX20 Modbus
client function is 100 ms, specify [1 ms],
[10 ms], or [50 ms] for the VZ20X [Data
acquisition interval] setting. In this
example, [1 ms] is selected.
4.2.2 Configuring GX20 Settings
(1) Modbus Client Function Settings
Basic settings
The menu locations vary depending on the setting method that is used.
■
GX/GP unit: MENU key > [Browse] tab > [Setting] > [Communication (Ethernet) settings] in Setting menu >
[Modbus client settings] > [Basic settings]
■
Web application: [Config.] tab > [Communication (Ethernet) settings] > [Modbus client settings]
■
Settings software: [Communication (Ethernet) settings] > [Modbus client settings]
Setting item
Setting value
On/Off
ON
Interval
100 ms
Wait time
2 min
Keep connection
Off
Connection timeout
1
37
TI 77V01B01-11EN
Oct.18, 2021-00