Manual Change for IM 01G05B03-01E 1st Edition : No.15-010-E July 30 2015-00
Changes to the section “7.2 Flow Totalizers” (page 43) :
Two of the key operations have been changed as below, requiring pressing the keys “three times” .
To reset the two flow totalizers to zero:
Press key
ON
O
three times when a totalizer is displayed.
To deactivate flow totalizing:
Press key
OFF
O
three times when a totalizer is displayed.
Addition to the section “14.5 Activation of a Pulse Output” (page 95) :
Maximum pulse output rate is 2 pulse per second (+/-20%).
Set the “Pulse Value” and the “Pulse Width” so that the actual maximum flow in the pipe is less than half
the displayed value (“Max – Value”).
Example:
The actual maximum flow 120m
3
/h
Pulse Value = 0.02m
3
Pulse Width = 150ms
INFO: Max – Value
240.0m
3
/h
Attention!
It is necessary to activate flow totalizers by pressing key
ON
O
to get the actual pulse
output. Refer to the section 7.2 (page 43) for flow totalizers.
Changes to the chapter “A Standard Specification” (page 109 to 116) :
Please use the following sheets for this chapter.