Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 2

Cold junction accuracy:

 0.04°C/°C after a warm-up of 

20 minutes.

Input impedance:

 > 1 M

W

.

Burn out

: full scale

Calibration:

 According to EN 60584-1.

Note: 

For TC wiring use proper compensating cable 
preferable shielded.

2.2.2  RTD Pt 100 Input

Input circuit:

 Current injection (135 µA).

Line resistance:

 Automatic compensation up to 20

W

/wire 

with maximum error ±0.1% of the input span.

Calibration: 

According to EN 60751/A2.

Note: 

The resistance of the 3 wires must be the same.

2.2.3  RTD Pt 1000 Input

2

3

Pt1000

Line resistance:

 Not compensated.

Pt 1000 input circuit:

 Current injection (15,5 µA).

Pt 1000 calibration:

 According to EN 60751/A2.

2.2.4  V and mV Input

mV

V

+

_

+

_

1

2

Input impedance:

 > 1 M

W

 for mV Input

 

500 k

W

 for Volt Input.

2.2.5  mA Input

0/4 to 20 mA input wiring for passive transmitter 

using the auxiliary pws

+

_

4 to 20 mA

Passive

transmitter

4

1

Input impedance:

 < 53

W

.

Internal auxiliary PWS: 

12 VDC (±10%), 20 mA max..

0/4 to 20 mA input wiring for passive transmitter 

using an external pws

+

_

+

_

1

2

0/4 to 20 mA

Passive

transmitter

_

External

PWS

+

0/4 to 20 mA input wiring for active transmitter

0/4 to 20 mA

Active

transmitter

+

_

+

_

1

2

2.2.6  Logic Input

Safety notes:

 

Do not run logic input wiring together with power cables;

 

The instrument needs 150 ms to recognize a contact 
status variation;

 

Logic inputs are 

NOT

 isolated by the measuring input.

A double or reinforced isolation between logic inputs and 
power line must be assured by the external elements.

Logic inputs driven by dry contact

Digital
Input 1

15

16

Maximum contact resistance:

 100

W

.

Contact rating:

  DI1 = 10 V, 6 mA;

2.3  OUTPUTS

Safety notes:

 

To avoid electrical shocks, connect power line at last.

 

For supply connections use No. 16 AWG or larger wires 
rated for at last 75°C.

 

Use copper conductors only.

 

SSR outputs are not isolated.  A reinforced isolation must 
be assured by the external solid state relays.

 

For SSR, mA and V outputs if the line length is longer than 
30 m use a shielded wire.

 

Do not short-circuit the terminals of the SSR output.

WARNING!  Before connecting the output actuators

we recommend to confi gure the parameters to 

Содержание TC 10-L

Страница 1: ...ust be mounted This is mandatory for FM approval 2 CONNECTION DIAGRAM RS485 TERMINALS Pin connector 1 4 mm max 0 055 in Stripped wire L 5 5 mm 0 21 in L ELECTRICAL CONNECTIONS Thermo couple DI1 OP3 Li...

Страница 2: ...20 mA input wiring for passive transmitter using an external pws _ _ 1 2 0 4 to 20 mA Passive transmitter _ External PWS 0 4 to 20 mA input wiring for active transmitter 0 4 to 20 mA Active transmitte...

Страница 3: ...5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 2 4 SERIAL INTERFACE D D D D D D D D RS 485 5 6 Interface type Isolated 50 V RS 485 Voltage levels According to EIA standard Protocol type...

Страница 4: ...Resolution 30000 counts Total Accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 200...

Страница 5: ...exceed SP at power on SP HYS PV A B D C EXCEEDED LAMP OUT LAMP lit off OUTPUT RELAY confirmation accepted lit off Energized De energized OFF OFF OFF Lit ON OFF Lit OFF Power ON OFF OFF ON OFF 5 3 HOW...

Страница 6: ...TC J 50 1000 C 58 1832 F crAL TC K 50 1370 C 58 2498 F S TC S 50 1760 C 58 3200 F r TC R 50 1760 C 58 3200 F t TC T 70 400 C 94 752 F n TC N 50 1300 C 58 2372 F Pt1 RTD Pt 100 200 850 C 328 1562 F Pt1...

Страница 7: ...9 13 o3F Out 3 function Available When the instrument has out 3 option Range nonE Output not used With this setting the status of the this output can be driven directly from serial link AL Alarm outpu...

Страница 8: ...1 0 ON off off AL1 off off off AL1 ON ON ON ON 3 The instrument does not store in EEPROM the alarm status For this reason the alarm status will be lost if a power down occurs 21 AL1L For High and low...

Страница 9: ...SE br Range 1 to 9999 engineering units Note For other details see 24 HAL1 parameter 32 AL2d Alarm 2 delay Available When 26 AL2t type is different form nonE Range From oFF 0 to 9999 seconds Note The...

Страница 10: ...ilable always but it is a read only parameter Range from 00 00 to 99 59 HH mm 42 Hi maximum measured value Available Available when 33 Hi Lo Hi high limit but it is a read only parameter Range Enginee...

Страница 11: ...a set point equal to the minimum value of the operative range e g 10 C When the temperature in the chamber is steady take note of the temperature measured by the reference system e g 9 C 3 Set 50 A L...

Страница 12: ...Exceeded indication EX OUT PK HI AL1 AL2 TC10 L Output b c d e The HI lamp d is ON When a measured value a is higher then the set point b EX lamp e lights OUT lamp b turns ON and the limit output rel...

Страница 13: ...onds 2 The upper display will show PASS while the lower display will show 0 3 By and buttons set the value assigned to 44 PAS2 Level 2 password Notes 1 The factory default password for configuration p...

Страница 14: ...n EN584 1 DIN 43710 1977 TC Type Ranges J 50 to 1000 C 50 0 to 999 9 C 58 to 1832 F 58 0 to 999 9 F K 50 to 1370 C 50 0 to 999 9 C 58 to 2498 F 58 0 to 999 9 F S 50 to 1760 C 50 0 to 999 9 C 58 to 320...

Страница 15: ...arm output Available ever Type SSR drive Isolation Not isolated Protection Output protected from short circuit Stato logico 1 12 V 20 23 mA Stato logico 0 0 5 V Auxiliary power supply for TX NOTE this...

Страница 16: ...ufacturing defects or faulty materials that are found within 18 months from manufacturing date The warranty is limited to the replacement of the instrument The tampering of the instrument or an improp...

Страница 17: ...ms behaviour 0 oFF to 20 0 s 1 7 bS PV input bias 100 to 100 of the input span dP 8 di A Digital Input action 0 DI1 direct 1 DI1 reverse OUT group N Param Description Range value or selection list ele...

Страница 18: ...Group N Param Description Range value or selection list elements Decimal gure 26 AL2t Alarm 2 type nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with a...

Страница 19: ...tion Range value or selection list elements Decimal gure 44 PAS2 Password level 2 0 oFF to 200 0 45 PAS3 Password level 3 3 to 200 0 46 di CL Display color 0 The display color is used to show the Exce...

Страница 20: ...Yokogawa Electric Corporation TC10 L ENGINEERING MANUAL PAG 20...

Отзывы: