4-23
IM 04L51B01-41EN
Using the Maintenance Console
1
2
3
4
5
10
App
■ To register a station number list
Enter the following items to create the station number list. Click
Save to module
to apply
the contents of the station number list to the wireless communication module.
Item
Description
Short address
Enter the short address (0001 to FFFD) of the router you want to add to the list.
Click
Add to list
to add the address along with the information entered in the
Station number
box to the list.
Station number
Enter the station number corresponding to the router’s short address.
Click
Add to list
to add the station number along with the information entered in
the
Short address
box to the list.
Note
If you register the station number list when there is no list in the MH920 Console International or
when a station number list has not been loaded from the wireless communication module, the
station number list registered in the wireless communication module will be deleted.
■ To delete information from the station number list
Enter a check mark in the Delete column of the entry you want to delete, and click
Remove
from list. The selected entry is deleted from the list. Click
Save to module
to apply the
contents of the station number list to the wireless communication module.
■ Loading the current settings from the wireless communication module
Click
Load from module
to load the current settings from the wireless communication
module. You can change the station number list based on the loaded information.
Note
Before loading the current settings from the wireless communication module, perform either of the
procedures below.
• Connect a wireless communication module with updated configuration, and then load the
settings by using
Load from module
in the Coordinator configuration window. For details, see
“Loading the current settings from the wireless communication module” in “Configuring the
Interface (Protocol setup tab)”.
• Load the setting from a configuration file saved in advance by using
Load Configuration
in the Coordinator configuration window. For details, “Loading the configuration file (Load
Configuration button)” in the Coordinator configuration window.
■ To save the station number list you edited
After setting the station number list, click
Save configuration
. The station number list is
saved with the specified file name in the specified folder. By default, the file is saved with the
following file name in the following folder.
• C:\OKI\MH920 Console International\Node_Log\MAC address_p3_NumList_date and time.
csv
* The MAC address is omitted if the file is saved without a wireless module connected.
■ To Load the station number list from a configuration file
Click
Load Configuration
to load a configuration file containing the station number list and
show the content of the file in the Maintenance console window.
4.5 Configuring the Coordinator Module