<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-9
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
Abs.
Index
Parameter
Sub-
Parameter
Label
Data Type/
Structure
Read/
Write
Initial value
Functional Description
90
HARD_REVISION
HW Version
OctetString
R/-
e.g. V1.00
Indicates transmitter's electronical
hardware version
91
PERCENT
Flow Percent
Float
R/-
-
Indicates flow value in % of scale span
92
PERCENT_UNIT
-
Unsigned16
R/-
1342: %
Fixed unit (%) of the percent indication
93
PRIMARY_VALUE
-
Float
R/-
-
Indicates flow value in arc length of
scale
94
PRIMARY_VALUE
_UNIT
-
Unsigned16
R/-
1013: mm
Fixed unit (mm) of the pointer position
95
DEVICE_STATUS1
Event Overview 1
Unsigned8
R/-
not active
Indicates 1st part of event overview
96
DEVICE_STATUS2
Event Overview 2
Unsigned8
R/-
0x10: Power Failure
(active)
Indicates 2nd part of event overview
97
DEFAULT_
CHANNEL
Default Channel
Unsigned16
R/-
Det. by ordered
scale
Indicates the process variable (index)
selected for channel transfer
98
EEPROM_
REVISION
EEPROM Version
Unsigned16
R/-
Cal-EEPROM
(high byte): e.g.
0x07: 7
Adj-EEPROM
(low byte): e.g.
0x08: 8
Indicates the revision of Cal- and
Adj-EEPROM
99
STATUS_
HANDLING
Flow Status
Handling
Unsigned8
R/W
0: Normal Status
Handling
Disables upper and lower measurement
range violation events (5 % to 105 %).
100
SCALE_SPAN_
UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Indicates the flow unit printed on the
scale
101
WTM_REVISION
WT-MAG Type
Unsigned8
R/-
30
Indicates the transmitter type
102
FBK_REVISION
Module Version
Unsigned8
R/-
30
Indicates the communication module
version
103
DISPLAY_
SELECT
Display Selection
Unsigned8
R/W
1: Total Value
Allows variable selection for local display
indication
104
OPER_DENSITY
Density
Float
R/-
Det. by ordered
scale
Indicates fluid's density value
105
OPER_DENSITY
_UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Configurated unit of fluid's density
106
FLOAT_BLOCKING
-
Record
R/-
-
Indicates and controls the float blocking
function
FLOAT_BLOCK_
ON
Float Blocking On
Unsigned8
R/-
0: Off
Enables and disables functionality
FLOAT_BLOCK_
LIMIT
Float Blocking
Limit
Unsigned8
R/-
0: 5 %
Sets lower limit value of supervision
range
FLOAT_BLOCK_
TIME
Float Blocking
Time
Unsigned8
R/-
0: Turbulent Flow
Sets reaction time according to flow type
FLOAT_BLOCK_
AZ_ON
Float Blocking
AZ On
Unsigned8
R/-
0: Off
Executes float blocking autozero
107
FLOAT_BLOCK_
AUTOZERO
Float Blocking
Autozero
Float
R/-
0.000
Indicates float blocking autozero value
108
LOW_FLOW_
CUTOFF_UNIT
Low Flow Cutoff
Unit
Unsigned16
R/-
Det. by ordered
scale
Indicates the unit of low flow cut-off
value
109
DEVICE_STATUS3
Event Overview 3
Unsigned8
R/-
Det. by ordered
scale
0x01: Volume Flow
Passivated
0x02: Mass Flow
Passivated
Indicates 3rd part of event overview
111
OPER_ACT_TIME
-
Record
R/-
-
Indicates the total powered operation
time
minutes
Operation Time
(Minutes)
Unsigned8
R/-
Delivery condition
Duration in minutes (0 to 59)
hours
Operation Time
(Hours)
Unsigned8
R/-
Delivery condition
Duration in hours (0 to 23)
days
Operation Time
(Days)
Unsigned16
R/-
Delivery condition
Duration in days
112
OPER_SDW_
TIME
-
Record
R/-
-
Indicates the total powered operation
time before last power down
minutes
Oper. Time Shadow
(Minutes)
Unsigned8
R/-
Delivery condition
Duration in minutes (0 to 59)
hours
Oper. Time Shadow
(Hours)
Unsigned8
R/-
Delivery condition
Duration in hours (0 to 23)
days
Oper. Time Shadow
(Days)
Unsigned16
R/-
Delivery condition
Duration in days
114
LONG_TAG
Electr. Long Tag
OctetString
R/W
Optionally det. by
ordered device
Indicates and changes transmitter's
Long Tag Number (32 characters)
230
VIEW_1
R/-
n.a.
Indicates a Profile defined parameter
preselection