5-9
IM 04P01B01-01E
Frequently Used Setup Operations (Setting Mode)
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
5.2 Setting the Alarm
The alarm is set for each channel.
If you change the input range, set the alarm again.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT
+
key to select
Alarm
and then press the
key.
3.
Set each item and press the key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
4.
When the
Setting complete
screen appears, do either of the following:
Press the key to set other channels.
If you are done, press the
ESC
key.
5.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Select the level number between 1 and 4.
Select On to set the alarm.
When set to On, the settings below can
be entered.
Set the channel range.
Select the alarm type.
Select the value used to turn On the
alarm.
Turn relay On when outputting alarms on
the relay. This setting is valid only on
models with the /A1, /A2, or /A3 option.
Specify the alarm relay No.
The new setting takes effect.
First channel Last channel
ESC/?
Set=Alarm
CH=01-01
Level=1
Alarm=Off
Type=H
Value= 1.000
Relay=Off
01-01 CH/level 1
Setting complete
Relay_No.=I01