3-5
IM 71M02D04-01E 10th Edition: 2012.12.01
Pin #
1
2
3
4
V
A
V
B
V
C
GND
2 1
4 3
3.3 Motor Terminal/Ground <TB2>
Terminal on Motor Side <CN8>
Housing:
172167-1 or 172338-1 (made by AMP)
Terminal:
170366-3 (made by AMP)
Manual tool : 755331-1 (made by AMP)
Cable Specifications
Cable Specification
Motor
AWG#20 (0.5mm
2
) or more, length 10 m or less
Optional cable: C1M-NA1-2061-
Ground
AWG#14 (2.0mm
2
) or more
(Use as thick a cable as possible.)
Class 3 ground (ground resistance 100
Ω
or less)
Tightening torque of the terminal screws:
1.2N-m (12kgf-cm) (terminal screws: M4 x 0.7)
Make sure to perform ground in order to avoid electric shock accidents. Moreover, make
sure to connect the GND terminals of the motor and the drive.
!
DANGER
Yokogawa's motor cables are twisted pair cables with a
common shield with the motor ground cable. The shield is
connected to the ground by connecting the motor ground cable
to the ground terminal.
If you provide your own cable, make sure to connect the shield
to the ground terminal. Connect the ground cable and motor
ground cable to one terminal and the shield to another terminal,
separately.
500W class: AWG#20
Insulation stripping length: 8 mm
Connector: 231-203/206-000
(made by WAGO)
Red
White
Black
Green or green/yellow
Ground: AWG#14
Motor cable
Crimp terminal: N2-4 (made by J.S.T.)