2-3
IM 71M02D04-01E 10th Edition: 2012.12.01
2.2 Installation of the Drive
Installation Location
•
Be sure to install the drive correctly in the control panel or on the machine.
•
If there are other heating elements near the drive, make sure to prevent the temperature
from becoming too high by installing a shield cover or similar protective device. Ensure
that the temperature around the drive does not exceed 50
°
C.
•
If there are vibration sources near the drive, install the drive using a vibration-proof
material.
•
Avoid installing the drive in an atmosphere with high temperature/high humidity or which
contains dust, dirt, metal powder, corrosive gasses, etc.
Drive environment
specification
Remarks
At operation
Ambient
temperature
0 ~ 50
°
C
Ambient
humidity
20 ~ 90% RH
There must be no
condensation.
At storage
Ambient
temperature
-20 ~ 85
°
C
Ambient
humidity
20 ~ 90% RH
There must be no
condensation.
Atmosphere
There must be no corrosive gasses, dirt or dust.
Must be used at an maximum altitude of 1000 meters
above sea level (CE mounting condition)
Installation Procedure
The drive is intended to be mounted on a vertical surface. Use the four mounting holes in the
die cast section, and mount the drive securely to a metal plate.
If you use flat washers, use washers whose external diameter is 8mm (ISO).
Wall (metal-made)
M4 screws in four places Tightening torque: 1.4N-m