<5. Parameter Summary>
5-7
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
Flg temp
EJX
Flg temp
Calculated flange temperature
value
RG
Flg Temp Coef
EJX
Flg Temp Coef
0
WG
Flg Temp Lim
EJX
Flg Temp Hi Alart
Val
Upper limit of Flange temperature
120 °C (deg C)
WG
Flg Temp Lo Alart
Val
Lower limit of Flange temperature
-40 °C (deg C)
WG
Fluct Variables
EJX
fDP
Average value of the sum of
squares of differential pressure/
pressure fluctuations
RG
fDP Status
Status of fDP
RG
fSPl
Average value of the sum of
squares of low-pressure-sidestatic
pressure fluctuations
RG
fSPl Status
Status of fSPl
RG
fSPh
Average value of the sum of
squares of high-pressure-side
static pressure fluctuations
RG
fSPh Status
Status of fSPh
RG
Loop test
Loop test
Test output setting
Within AO lower and upper
limits
M
Test Auto Release
Time
Auto release time for the test
function. Coverage is Loop test,
DO test and Device Variable
Simulation.
10min, 30min, 60min, 3h,
6h, 12h
10 min
W
Low cut
Low cut
Low cut
0.00 to 20.00%
Refer to
subsection
3.2.6
W
Low cut mode
Low cut mode
Linear or Zero
Linear
W
Master test
Master test
Software reset and self test
M
Message
Message
Message
32 alphanumerics
As specified
W
Number of
requested
preambles
Num req preams
Number of requested preambles
R
Num resp preams
HART 7
Number of response preambles
5
W
Optional
function
Option Password
HART 7
Optional function activation
password
W
Piping
orientation
H/L Swap
Impulse piping accessing direction Normal or Reverse
Normal
WD
Poll address
Poll addr
Poll address for multidrop use
0 to 15(HART 5), 0 to
63(HART 7)
0
W
Loop current mode
HART 7
Loop current mode in Multi Drop
mode
(Disabled, Enabled)
Disabled
W
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
*4:
For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.