<3. Parameter Setting>
3-26
IM 01C25T01-06EN
3.3.15 Test Output, Simulation, and Squawk
NOTE
Fixed current output, DO Test, and Device
Variable Simulation Function continue for a given
holding time, then is released automatically.
Even if the HART configuration tool power
supply is turned off or the communication cable
is disconnected, the test output will continue for
that time.
The holding time can be selected from 10 min*,
30 min, 60 min, 3 hour, 6 hour or 12 hour.
*: Default value.
• Procedure to call up the display
DD
[Root Menu]
→ Diag/Service →
Test Auto Release Time
DTM (excluding
EJX_HART 5
[1.2])
[Root Menu]
→ Diag/Service →
Test → Test Auto Release Time
EJX_HART 5[1.2]
DTM
Diag and Service → Service
→ Test Auto Release Time
(1) Fixed current output
This feature can be used to output a fixed current
(or voltage) for loop checks. The available range for
test output depend on the settings for the
AO lower
limit
and
AO upper limit
parameters, whose limit
is from 3.6 mA or 0.9 V (-2.5%) to 21.6 mA or 5.4 V
(110%).
Refer to the subsection 3.3.2 about the setting of
AO lower limit
and
AO upper limit
.
While this function works, “TEST” is displayed on
the integral indicator.
Setting by DD and DTM (EJX HART 5 DTM
based on FDT1.2)
Call up the test output parameter (Loop test) and
select the output signal.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Diag/Service →
Test (DTM only) → Loop test →
Display Item
Contents
4mA (1V*)
Output a 4mA (1V*) DC signal
20mA (5V*)
Output a 20mA (5V*) DC signal
Other
Set a desired output signal value
End
Exit
*:
For 1 to 5 V output.
Setting by EJX HART 5 DTM based on
FDT1.2
Call up the test output parameter (Loop test) and
select either manual test or auto test, and set the
current value.
• Procedure to call up the display
EJX HART 5
DTM based on
FDT1.2
Diag and Service → Service
→ Loop test →
Display Item
Contents
Manual Test
Set the current value or % value at
Test output value
, then click the
Start button.
Auto Test
Set the interval and rate of change
of current output at
Auto Test
Setting
, then click the Start button.
(2) DO Test (only for EJX series)
EJX
This function performs the contact output test.
(option code: /AL)
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Detailed setup
→Output condition → Process
Alerts → DO config → DO Test →
EJX_HART 5[1.2]
DTM
Diag and Service → Service → DO
test →
Display Item
Contents
Off
Contact output: OFF
On
Contact output: ON
Exit
Output test is canceled