<5. Parameter Summary>
5-6
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
Event
Notification
4-20mA
Event Notification
Retry Time
HART 7
Event Notification Retry Time
R
Max Update Time
HART 7
Max Update Time for Event
Notification
R
Event Debounce
Interval
HART 7
Event Debounce Interval
Debounce Interval to detect
an event.
R
Acknowledge Event
Notification
HART 7
Acknowledge Event Notification
W
Event Status
HART 7
Event Status
0x00 Approved event or no
event
0x10 Configuration changed
event pending
0x20 Device status event
pending
0x40 More status available
event pending
R
Event Number
HART 7
Event Number
W
Time First Unack
Event Triggered
HART 7
Time First Unack Event Triggered
W
Latched Cfg chng
count
HART 7
Latched Cfg chng count
W
Latched Device
Status
HART 7
Device status when event occurred
W
Latched Status
group 1 to 10
HART 7
Field device status when event
occured
W
Latched Ext dev
status
HART 7
Latched Device
Diagnostic Status 0
HART 7
Latched Device
Diagnostic Status 1
HART 7
Latched AO
saturated
HART 7
Latched AO fixed
HART 7
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
*4:
For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.