<APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE>
A3-14
IM 01F06F00-01EN
LCD
Display Alarm Detail
DI1 Block
DI2 Block
PID Block
IT Block
AR Block
Alarm Reset SW*
(default)
AL-77 AI3 in Man
Mode (AL-77)
Provided
(OFF)
AL-78 AI3 Simulation
Active (AL-78)
Provided
(OFF)
AL-79
AI3 Not
Scheduled
(AL-79)
Provided
(OFF)
AL-80 IT in Man
Mode (AL-80)
<OUT.Status>
• Default
Good(NC)-Non
Specific
• STATUS_OPTS:
Uncertain if Man
mode = Active
Uncertain-Non
Specific
Provided
(OFF)
AL-81
IT Not
Scheduled
(AL-81)
Provided
(OFF)
AL-82
IT Total
Backup Err
(AL-82)
<BLOCK_ERR>
Lost NV Data
Provided
(OFF)
<OUT.Status>
(OFF)
Bad-Device Failure
AL-83 IT Conf. Err
(AL-83)
<BLOCK_ERR>
Configuration Error
Provided
(OFF)
AL-84 AR in Man
Mode (AL-84)
<OUT.Status>
• Default
Good(NC)-Non
Specific
• STATUS_OPTS:
Uncertain if Man
mode = Active
Uncertain-Non
Specific
Provided
(OFF)
AL-85
AR Not
Scheduled
(AL-85)
Provided
(OFF)
AL-86
AR Range
Conf. Err
(AL-86)
<BLOCK_ERR>
Configuration Error
Provided
(OFF)
AL-87
AR Temp. IN
Over Range
(AL-87)
<OUT.Status>
Uncertain-Non
Specific
Provided
(OFF)
AL-88
AR Press IN
Over Range
(AL-88)
<OUT.Status>
Uncertain-Non
Specific
Provided
(OFF)
AL-89
AR Flow
IN Not
Connected
(AL-89)
<OUT.Status>
Bad-Non Specific
Provided
(OFF)
AL-90
AR Temp.
IN Not
Connected
(AL-90)
<OUT.Status>
Bad-Non Specific
Provided
(OFF)
AL-91
AR Press
IN Not
Connected
(AL-91)
<OUT.Status>
Bad-Non Specific
Provided
(OFF)
AL-92
AR Comp.
Coef.Conf. Err
(AL-92)
<BLOCK_ERR>
Configuration Error
Provided
(OFF)
<OUT.Status>
Bad-Non Specific
AL-93
AR Output
Unit Conf. Err
(AL-93)
<BLOCK_ERR>
Configuration Error
Provided
(OFF)
<OUT.Status>
Bad-Configuration
Error