![YOKOGAWA ADMAG AXF Series Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/yokogawa/admag-axf-series/admag-axf-series_user-manual_911181035.webp)
IM 01E20F02-01E
5-10
5. EXPLANATION OF BASIC ITEMS
Arithmetic Out
The display is given in the same manner as Integrator
Out, decimal point is set by
"AR:OUT_RANGE.Decimal_Point".
AR:OUT_RANGE.Decimal_Point
AR:OUT_RANGE.Decimal_Point
Desimal Point
Location
Example
0
0
12345678
1
1
1234567.8
2
2
123456.78
3
12345.678
4
1234.5678
5
123.45678
6
12.345678
7
3
4
5
6
7
1.2345678
Other
0
12345678
T0513.eps
PD Tag
The third line shows the example of PD Tag display.
Maximum number of figures is 16, on LCD the head
16 charactors out of 32 charactors of management PD
Tag can be displayed.
1 2 3
.
4 5
l / h
6
8 7 6 5 4
M l
9
T A G
F R
I T 1
A X F - P l
1
e
c
a
F0511.eps
Adhesion Check
When Adhesion Check display is selected result is
displayed as below showing the level number.
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
2
F0512.eps
Adhesion Check Level Judge
Level4 : Adh Measure Value > Adhesion Level4
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
4
F0513.eps
Level3 : Adhesion Level4
Adh Measure Value >
Adhesion Level3
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
3
F0514.eps
Level2 : Adhesion Level3
Adh Measure Value >
Adhesion Level2
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
2
F0515.eps
Level1 : Adhesion Level2
Adh Measure Value >
Adhesion Level1
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
1
F0516.eps
Level0 : Adhesion Level1
Adh Measure Value
1 2 3
.
4 5
l / h
6
L e
F R
A D H
:
v e l
0
F0517.eps
Communication
The third line shows the example of Communication
display.
1 2 3
.
4 5
l / h
6
8 7 6 5 4
M l
9
C O M
F R
I T 2
d a t
i o n
F o u n
d b u s
F i e l
F0518.eps
5.6.2 Display Modes
ADMAG AXF has following display modes.
- Normal Display
- Alarm Display
- Warning Display
- Autozero Display
Display Renewal Time
Display renewal time for each display modes depends
on Display Cycle setting;
2s,1s,400ms,200ms
4s
8s
Normal Display
2s
4s
8s
Alarm Display
4s
4s
8s
Warning Display
4s
4s
8s
Autozero Display
Display Cycle set Time
30s
Display Mode
T0514.eps
Normal Display
In this display mode various flow data from one to
three lines are displayed as described in 5.5.1.