IM 01E20F02-01E
5-8
5. EXPLANATION OF BASIC ITEMS
5.6 Integral LCD Indicator
Employing 32*132 full dot matrix backlit LCD,
various display can be obtained.
5.6.1 Flow Data Display
By the transducer block parameters setting in
DISPLAY_SELECT1, 2, 3 as described in 5.3, up to
three lines display can be made among the following
data.
-Flow Rate(%)
-Flow Rate
-Flow Rate(Bar)
-Integrator1 Out
-Integrator2 Out
-Arithmetic Out
-PD Tag
-Adhesion Check
-Communication
The number of the data can be configured by setting
DISPLAY_SELECT1, 2, 3 as follows;
1 line display
2 line display
3 line display
Display Select1
-
-
-
Display Select2
Off
Other than "Off"
Other than "Off"
Display Select3
-
Off
Other than "Off"
T0507.eps
The data titles are displayed together with the flow
data and units.
F R
I T 1
I T 2
T A G
A D H
C O M
: Flow Rate, Flow Rate(%)
: Integrator1 Out
: Integrator2 Out
: Arithmetic Out
: PD Tag
: Adhesion Check
: Communication
A R
F0504.eps
Flow Rate (%)
1 0 0 . 0
%
F R
F0505.eps
Decimal point is always to the first place.
Flow Rate
Flow rate is displayed together with the units set in
XD_SCALE, the maximum number of figures is six.
- 1 2 3 . 4 5 6
k g a l /
i n
m
F R
F0506.eps
In the case of L_TYPE is "Direct " decimal point
location of the data becomes as follows.
XD_SCALE.Decimal_Point
XD_SCALE.Decimal_Point
Desimal
Desimal
Point
Point
Location
Location
Example
Example
0
0
123
1
1
123.4
2
2
3
123.45
3
123.456
Other
Auto
Refer to below
T0508.eps
When XD_SCALE.Units_Index is set as Other decimal
point location of the data becomes as follows.
XD_SCALE.EU_0,EU_100
XD_SCALE.EU_0,EU_100
set
set value
value
Desimal Point
Desimal Point
Location
Location
Example
Example
XD_SCALE value
-10000
0
-33333
-10000 < XD_SCALE value
-1000
1
-4444.1
-1000 < XD_SCALE value
-100
2
-555.12
-100 < XD_SCALE value
-10
3
-66.123
-10 < XD_SCALE value < 10
3
-7.123
0.123
10
XD_SCALE value < 100
3
66.123
100
XD_SCALE value < 1000
2
555.12
1000
XD_SCALE value < 10000
1
4444.1
10000
XD_SCALE value
0
33333
T0509.eps
*XD_SCALEvalue : Max (|XD_SCALE.EU0|, |XD_SCALE.EU100|)
When the flow data exceeds the maximum number of
figures six, then "84:Disp Over Wng" message is
displayed.
9 9 9
.
9 9
l / h
9
2 3 4 5 6
M l
1
I T 1
F R
p
D
8 4 :
i s
n g
r
W
e
O v
F0507.eps