8. REMOTE SWITCH-OFF

The device has two inputs (AUX) for connecting a potential-free contact to which a telephone dialler can be 
connected, for example, to remotely switch the thermostat on and off using a telephone.
The contact can be in one of the following positions:
- open: normal operation (according to the programming set via keypad). 
- closed: thermostat in off operation.
The remote off condition is indicated on the display by the flashing of the symbol 

 to differentiate it from the 

keypad off 

 condition.

Note:

  This function must be operated via the Advanced Configuration (ADV) menu. The auxiliary input parameter 

must be set to “diG”.

IMPORTANT:

 Remote off condition (contact closed) takes priority over any other programming and therefore 

the thermostat will remain in the off condition until the contact returns to the open position.

9. THERMOSTAT RESET

This can be used to delete any settings made and reload the default settings. 
Proceed as follows:

Disconnect the thermostat from the wall base and reconnect it.
 While the buttons are flashing, keep the button 

 pressed until “dEF” appears on the display.

Resetting to default settings will clears all settings in the configuration parameters: 

Time and date
Edit programs
Change temperature (T1), T2, T3
Timer setting 
Advanced menu configurations

IMPORTANT: 

Resetting to default parameters will not delete the wireless configurations made on the thermostat. 

To delete the wireless configurations, see chapter “

7.6.6. Def 25 : Thermostat wireless configuration reset

”.

10. INSTALLATION

10.1. SAFETY WARNINGS

The following instructions must be observed when installing the product:

The product must be installed by a qualified professional, scrupulously respecting the wiring diagram.
Do not power or connect the product if any of its parts are damaged. Do not carry out repairs and contact 
technical support directly.
Do not use the product for purposes other than those specified.
The  device  must  be  installed  and  put  into  operation  in  accordance  with  current  legislation  on  electrical 
systems.
The product can be used in a category 3 and grade 2 pollution measurement environment.
Where it is necessary to guarantee galvanic insulation towards the boiler, it is essential to install the REL1C 
accessory (see diagram SD541-6054 in the MTR2000 product card).

10.2. HOW TO START THE THERMOSTAT

The Thermarp accessory is ideal for wall mounting. Alternatively, it can be installed on a flush mounting box
Mod. 503. 
The thermostat must be installed at a height of about 1.5 m above the floor, protected from direct radiation, 
away from doors, windows, heat sources, positions with excess or total lack of ventilation.

The YOKIS THERMARP thermostat runs on batteries (2 x 1.5 V AAA / LR03 type batteries).

Fix the base to the wall using the screws provided.
Open the rear compartment of the thermostat timer to 

insert the batteries

, checking the polarity indicated  

on the battery compartment.

1.
2.





1.
2.

3.
4.

5.
6.

1.
2.

Содержание Thermarp

Страница 1: ...DIGITAL THERMOSTAT WITH DIRECT OR WIRELESS CONNECTION INSTALLATION PROGRAMMING AND USE INSTRUCTION MANUAL Thermarp Cod 5454489...

Страница 2: ...2 Proportional adjustment TPI 1 warm up only 17 7 5 3 3 Emergency control winter operation only 18 7 5 4 Antifreeze temperature 19 7 5 5 Auxiliary input management 19 7 5 6 Keypad locking password 19...

Страница 3: ...RO Single zone thermostat configuration with wireless connection MTR 32 10 4 6 Configuration of multiple thermostats one in each zone in a multi zone system 33 11 REPLACING THE BATTERIES 36 12 TECHNIC...

Страница 4: ...even in the dark 1 1 MAIN FEATURES Summer and winter operating modes Model available in white 1 5V AAA type battery power supply Seven programs available for heating or cooling operation Capacitive to...

Страница 5: ...m for the current day in automatic operation 8 Indicators Active load in summer cooling mode Manual operation active Active load in winter heating mode Hours and minutes The functions on the keypad va...

Страница 6: ...nce temperatures T1 T2 and T3 can be set in the Configuration menu 3 MANUAL OPERATION In manual operation the thermostat behaves like a normal thermostat adjusting according to the Tm manual setpoint...

Страница 7: ...ng Confirm the Tm setpoint or change it if required using buttons and Press to confirm the selection At this point the room temperature value reappears and the thermostat operates in manual mode To sw...

Страница 8: ...ssed until the symbol appears on the display To reactivate the adjustment hold button pressed for about three seconds MANUAL OR AUTOMATIC OPERATION 3s 3s 6 MINIMUM AND MAXIMUM VALUES In any operating...

Страница 9: ...configurations see Parag 7 5 Radio frequency menu Hold button pressed for longer than 3 seconds to open configuration mode The following block chart summarises CONFIGURABLE PARAMETERS 7 CONFIGURATION...

Страница 10: ...ings By default the thermostat is configured to switch to daylight saving time on the last Sunday in March at 02 00 a m and to switch back to standard time on the last Sunday in October at 03 00 a m a...

Страница 11: ...d Sunday program profiles can be found at the bottom of the booklet You can change this configuration if it does not meet your needs In particular for every day of the week you can choose a specific p...

Страница 12: ...When all the changes have been made exit the configuration menu by holding the button pressed 7 3 CHANGE TEMPERATURES T1 T2 T3 This menu can be used to change the three automatic operation temperature...

Страница 13: ...fter which the system it switches to off operation 7 4 3 Off timed If a timer is set to the off state off state is maintained until the end of the timer after which the system switches to the operatio...

Страница 14: ...ation hold button pressed or wait for the timeout approx 40 seconds 7 5 ADVANCED CONFIGURATION MENU Using the advanced configuration menu ADV it is possible to modify or display the following operatin...

Страница 15: ...ADVANCED PARAMETERS Summer Winter Antifreezetemp Auxiliary input Keypad password Timefunction System SW version HW version 7 5 1 7 5 4 7 5 5 7 5 6 7 5 7 7 5 8 7 5 9 7 5 Band Period 7 5 2 7 5 3 Prop W...

Страница 16: ...5 3 Adjustment parameters In the case of on off adjustment rEG 0 the only parameter to be set is the differential dIF which can assume values between 0 1 C and 1 C parameter to be set also for coolin...

Страница 17: ...heating off time and can take values of 10 20 or 30 minutes During operation at the beginning of the control period the thermostat measures the room temperature TA and compares it with the setpoint Ac...

Страница 18: ...e to the optimum with very similar floor and ceiling temperatures Radiator systems and especially connector systems generate a higher gradient curve in which the ceiling temperature is higher than the...

Страница 19: ...ler if you want to connect an external temperature sensor 7 5 6 Keypad locking password It is possible to set a keyboard which is useful if the thermostat is installed in public places or if you want...

Страница 20: ...econds 7 6 RADIO FREQUENCY MENU The RF menu item provides access to all the wireless settings of the thermostat Connected MTR wireless actuator connection test Configuration reception from AppPRO as C...

Страница 21: ...The following figure summarises the navigation through the various radio frequency menu items TestRF TestRF STOP ConnE2 RecE5 APE7 defc24 defc25 Pass or ER 16 ConnE2 Pass or ER 17 RecE5 Pass or ER 17...

Страница 22: ...return directly to the beginning of the radio frequency menu IMPORTANT There is no timeout to release the thermostat from RF Test condition 7 6 2 Configuration reception from AppPRO Although this menu...

Страница 23: ...nd until def c24 appears Then press button to run the function which immediately erases all access points If the programming is performed correctly the message PASS will appear on the thermostat to co...

Страница 24: ...less configurations made on the thermostat To delete the wireless configurations see chapter 7 6 6 Def 25 Thermostat wireless configuration reset 10 INSTALLATION 10 1 SAFETY WARNINGS The following ins...

Страница 25: ...ANT The maximum distance between Thermarp and a Yokis receiver is 250 m in open range inside a 100 m2 house with perpendicular crossing of a master wall or floor slab These values may be reduced by th...

Страница 26: ...7 Seconds synchronisation Minute synchronisation Hour synchronisation Setting the year Month settings Day settings Time Day Temperature Program chart At this point the thermostat will start operating...

Страница 27: ...smaller than 0 5 mm2 must comply with IEC 60332 2 2 In the case of a wireless receiver before pairing the thermostat and the wireless receiver the MTR2000ERP X or MTR2000MRP X receiver must be wired...

Страница 28: ...e it is essential to install the REL1C accessory see diagram SD542 6054 in the MTR2000 product card Single zone wiring via MTR2000ERP X 1 2 3 4 5 6 Multi zone wiring with OR function 1 2 3 4 5 6 Zone...

Страница 29: ...his case it is possible to configure the thermostat locally using only its configuration menus It is obviously necessary to configure the wireless connection with the MTR2000ERP X or MTR2000MRP X rece...

Страница 30: ...wireless bus temporarily move the thermostat to near the module that controls the boiler Pair the THERMARP thermostat with the module that controls the boiler following the steps described above 3 Set...

Страница 31: ...turn directly to the beginning of the radio frequency menu IMPORTANT There is no timeout to release the thermostat from RF Test condition Note When configured in this way the thermostat cannot be acce...

Страница 32: ...stat cannot be accessed remotely or locally via the Yno app To be so a Yokis Hub must also be also installed in the system 10 4 5 YOKIS PRO Single zone thermostat configuration with wireless connectio...

Страница 33: ...Configuration of multiple thermostats one in each zone in a multi zone system This is typically the case in a single family house with several floors where the heating is managed by means of a zone s...

Страница 34: ...e also installed in the system Case B Simply follow the instructions in the two previous paragraphs for each thermostat according to whether or not you use the Yokis PRO app for configuration Single z...

Страница 35: ...ge the device to be controlled at the label On the screen that appears select the MTR with the boiler symbol and confirm Note This boiler MTR must be connected on all of the system as a multi zone rel...

Страница 36: ...C T3 0 1 C 23 0 C T3 summer T2 50 0 C 0 1 C 25 0 C antifreeze temperature 1 0 C 50 0 C 0 1 C 6 0 C operating mode winter summer winter adjustment type ON OFF PROP ON OFF ON OFF differential 0 1 C 1 0...

Страница 37: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P7 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P1 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20...

Страница 38: ...DS1054 057 P38...

Страница 39: ...P39 DS1054 057...

Страница 40: ...54 057 P40 Urmet S p a 10154 TORINO ITALY Via Bologna 188 C For technical information go to www yokis com or call Customer Service 39 011 23 39 810 export dept Phone 011 24 00 250 256 Fax 39 011 24 00...

Отзывы: