background image

DS1054-057

P1

If  no  program  exactly  meets  your  needs,  choose  the 
program that comes closest and press 

 a second time 

to access the program profile edit.
The  time  indicator  shows  00:00,  the  temperature  level 
icon  (T1,  T2  or  T3)  and  the  vertical  bar  corresponding 
to the time flash. Press button 

 or 

 to change the 

temperature level and button 

 to move on to the next 

hour. Set the desired temperature level for each hour of 
the day.
For  each  hour,  it  is  also  possible  to  delay  the  start  of 
adjustment by 15’, 30’ or 45’ minutes. After setting the 
temperature  as  described  above,  press  and  hold  the 
button 

  for  3  seconds  to  set  a  delay.  The  minute 

indicator will start flashing. Using button 

 or 

 set 

the delay time and press button 

 to confirm and move 

to the time hour.

6.

7.

8.

When the program has been edited as required, go back to the day selection page by pressing button 

 

twice and repeat, if necessary, the operations described above for the other days of the week. When all the 
changes have been made, exit the configuration menu by holding the button 

 pressed.

7.3. CHANGE TEMPERATURES (T1), T2, T3 

This menu can be used to change the three automatic operation temperatures. 
Proceed as follows to edit the program:

On the operating screen, hold button 

 pressed for three seconds. The icon 

 will start flashing on the 

display.
 Briefly press button 

 until the symbol 

 flashes. Press button 

 to access the parameter editing function. 

The icon 

 will stop flashing.

Once all the parameters have been set, press the button 

 to exit and return to the programming menu. 

The icon 

 will stop flashing. To exit and go back to normal operation, hold pressed 

 or wait for the 

timeout (approx. 40 seconds).

(*)IMPORTANT!: 
T1 cannot be configured in cooling mode.
The set temperature values must comply with the condition: (T1)* ≤ T2 ≤ T3.

9.

1.

2.

6.

 The T1 temperature value will flash. Change the value using 
buttons 

 and 

 and press the button 

 to confirm and 

go to editing T2.
Change  the  value  using  buttons 

  and 

  and  press  the 

button 

 to confirm and go to editing T3.

Change  the  value  using  buttons 

  and 

  and  press  the 

button 

 to go back to the T1 temperature editing page.

3.

4.

5.

Содержание Thermarp

Страница 1: ...DIGITAL THERMOSTAT WITH DIRECT OR WIRELESS CONNECTION INSTALLATION PROGRAMMING AND USE INSTRUCTION MANUAL Thermarp Cod 5454489...

Страница 2: ...2 Proportional adjustment TPI 1 warm up only 17 7 5 3 3 Emergency control winter operation only 18 7 5 4 Antifreeze temperature 19 7 5 5 Auxiliary input management 19 7 5 6 Keypad locking password 19...

Страница 3: ...RO Single zone thermostat configuration with wireless connection MTR 32 10 4 6 Configuration of multiple thermostats one in each zone in a multi zone system 33 11 REPLACING THE BATTERIES 36 12 TECHNIC...

Страница 4: ...even in the dark 1 1 MAIN FEATURES Summer and winter operating modes Model available in white 1 5V AAA type battery power supply Seven programs available for heating or cooling operation Capacitive to...

Страница 5: ...m for the current day in automatic operation 8 Indicators Active load in summer cooling mode Manual operation active Active load in winter heating mode Hours and minutes The functions on the keypad va...

Страница 6: ...nce temperatures T1 T2 and T3 can be set in the Configuration menu 3 MANUAL OPERATION In manual operation the thermostat behaves like a normal thermostat adjusting according to the Tm manual setpoint...

Страница 7: ...ng Confirm the Tm setpoint or change it if required using buttons and Press to confirm the selection At this point the room temperature value reappears and the thermostat operates in manual mode To sw...

Страница 8: ...ssed until the symbol appears on the display To reactivate the adjustment hold button pressed for about three seconds MANUAL OR AUTOMATIC OPERATION 3s 3s 6 MINIMUM AND MAXIMUM VALUES In any operating...

Страница 9: ...configurations see Parag 7 5 Radio frequency menu Hold button pressed for longer than 3 seconds to open configuration mode The following block chart summarises CONFIGURABLE PARAMETERS 7 CONFIGURATION...

Страница 10: ...ings By default the thermostat is configured to switch to daylight saving time on the last Sunday in March at 02 00 a m and to switch back to standard time on the last Sunday in October at 03 00 a m a...

Страница 11: ...d Sunday program profiles can be found at the bottom of the booklet You can change this configuration if it does not meet your needs In particular for every day of the week you can choose a specific p...

Страница 12: ...When all the changes have been made exit the configuration menu by holding the button pressed 7 3 CHANGE TEMPERATURES T1 T2 T3 This menu can be used to change the three automatic operation temperature...

Страница 13: ...fter which the system it switches to off operation 7 4 3 Off timed If a timer is set to the off state off state is maintained until the end of the timer after which the system switches to the operatio...

Страница 14: ...ation hold button pressed or wait for the timeout approx 40 seconds 7 5 ADVANCED CONFIGURATION MENU Using the advanced configuration menu ADV it is possible to modify or display the following operatin...

Страница 15: ...ADVANCED PARAMETERS Summer Winter Antifreezetemp Auxiliary input Keypad password Timefunction System SW version HW version 7 5 1 7 5 4 7 5 5 7 5 6 7 5 7 7 5 8 7 5 9 7 5 Band Period 7 5 2 7 5 3 Prop W...

Страница 16: ...5 3 Adjustment parameters In the case of on off adjustment rEG 0 the only parameter to be set is the differential dIF which can assume values between 0 1 C and 1 C parameter to be set also for coolin...

Страница 17: ...heating off time and can take values of 10 20 or 30 minutes During operation at the beginning of the control period the thermostat measures the room temperature TA and compares it with the setpoint Ac...

Страница 18: ...e to the optimum with very similar floor and ceiling temperatures Radiator systems and especially connector systems generate a higher gradient curve in which the ceiling temperature is higher than the...

Страница 19: ...ler if you want to connect an external temperature sensor 7 5 6 Keypad locking password It is possible to set a keyboard which is useful if the thermostat is installed in public places or if you want...

Страница 20: ...econds 7 6 RADIO FREQUENCY MENU The RF menu item provides access to all the wireless settings of the thermostat Connected MTR wireless actuator connection test Configuration reception from AppPRO as C...

Страница 21: ...The following figure summarises the navigation through the various radio frequency menu items TestRF TestRF STOP ConnE2 RecE5 APE7 defc24 defc25 Pass or ER 16 ConnE2 Pass or ER 17 RecE5 Pass or ER 17...

Страница 22: ...return directly to the beginning of the radio frequency menu IMPORTANT There is no timeout to release the thermostat from RF Test condition 7 6 2 Configuration reception from AppPRO Although this menu...

Страница 23: ...nd until def c24 appears Then press button to run the function which immediately erases all access points If the programming is performed correctly the message PASS will appear on the thermostat to co...

Страница 24: ...less configurations made on the thermostat To delete the wireless configurations see chapter 7 6 6 Def 25 Thermostat wireless configuration reset 10 INSTALLATION 10 1 SAFETY WARNINGS The following ins...

Страница 25: ...ANT The maximum distance between Thermarp and a Yokis receiver is 250 m in open range inside a 100 m2 house with perpendicular crossing of a master wall or floor slab These values may be reduced by th...

Страница 26: ...7 Seconds synchronisation Minute synchronisation Hour synchronisation Setting the year Month settings Day settings Time Day Temperature Program chart At this point the thermostat will start operating...

Страница 27: ...smaller than 0 5 mm2 must comply with IEC 60332 2 2 In the case of a wireless receiver before pairing the thermostat and the wireless receiver the MTR2000ERP X or MTR2000MRP X receiver must be wired...

Страница 28: ...e it is essential to install the REL1C accessory see diagram SD542 6054 in the MTR2000 product card Single zone wiring via MTR2000ERP X 1 2 3 4 5 6 Multi zone wiring with OR function 1 2 3 4 5 6 Zone...

Страница 29: ...his case it is possible to configure the thermostat locally using only its configuration menus It is obviously necessary to configure the wireless connection with the MTR2000ERP X or MTR2000MRP X rece...

Страница 30: ...wireless bus temporarily move the thermostat to near the module that controls the boiler Pair the THERMARP thermostat with the module that controls the boiler following the steps described above 3 Set...

Страница 31: ...turn directly to the beginning of the radio frequency menu IMPORTANT There is no timeout to release the thermostat from RF Test condition Note When configured in this way the thermostat cannot be acce...

Страница 32: ...stat cannot be accessed remotely or locally via the Yno app To be so a Yokis Hub must also be also installed in the system 10 4 5 YOKIS PRO Single zone thermostat configuration with wireless connectio...

Страница 33: ...Configuration of multiple thermostats one in each zone in a multi zone system This is typically the case in a single family house with several floors where the heating is managed by means of a zone s...

Страница 34: ...e also installed in the system Case B Simply follow the instructions in the two previous paragraphs for each thermostat according to whether or not you use the Yokis PRO app for configuration Single z...

Страница 35: ...ge the device to be controlled at the label On the screen that appears select the MTR with the boiler symbol and confirm Note This boiler MTR must be connected on all of the system as a multi zone rel...

Страница 36: ...C T3 0 1 C 23 0 C T3 summer T2 50 0 C 0 1 C 25 0 C antifreeze temperature 1 0 C 50 0 C 0 1 C 6 0 C operating mode winter summer winter adjustment type ON OFF PROP ON OFF ON OFF differential 0 1 C 1 0...

Страница 37: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P7 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 P1 T3 T2 T1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20...

Страница 38: ...DS1054 057 P38...

Страница 39: ...P39 DS1054 057...

Страница 40: ...54 057 P40 Urmet S p a 10154 TORINO ITALY Via Bologna 188 C For technical information go to www yokis com or call Customer Service 39 011 23 39 810 export dept Phone 011 24 00 250 256 Fax 39 011 24 00...

Отзывы: