background image

 

11 

COOLING WATER PIPING 

 

If  possible,  the  cooling  tower  should 

be  installed  at  the  same  level  or  above 
the  level  of  the  chiller.    If  this  is  not 
possible, give careful consideration to the 
prevention  of  drain-back  and  loss  of 
cooling  water  due  to  overflow  of  the 
tower.  Such matters must be given prior 
consideration by the design engineer. 

As  with  the  chilled  water  connections, 

a  balance  valve  should  be  installed  on 
the  cooling  water  inlet  and  a  stop  valve 
installed  on  the  cooling  water  outlet.  
Both  valves  should  be  in  close  proximity 
to the chiller.  After thoroughly testing for 
leaks, insulate the piping circuit, ensuring 
an  adequate  vapor  barrier  is  obtained.  
Be  sure  to  allow  access  to  any  valves, 
wells,  and  ports  that  may  be  present.  
Also,  ensure  the  chiller  panels  are  not 
restricted by the insulation. 

Additionally, there should be flush and 

drain  valves  installed  between  the 
machine  and  the  balance/stop  valves  so 
as  to  allow  for  flushing  of  the  absorber-
condenser  coils  should  it  ever  become 
necessary. 

 

CAUTION

 

1. DO  NOT  EXCEED  100 

–  120%  OF 

STANDARD 

COOLING 

WATER 

FLOW. 

2. DO NOT EXCEED 85.3 PSI (588 kPa) 

IN THE COOLING WATER CIRCUITS 
AT THE ABSORPTION CHILLER. 

3. DO  NOT  INSTALL  ANY  VALVES  IN 

EXPANSION LINES, WHEN USED. 

 

Figure 9 

– Cooling Water Piping

 

 

 

HEAT MEDIUM PIPING 

 

The Heat  Medium Piping contains  the 

hot water to drive the absorption system.  
As  long  as  this  water  remains  between 
158-203°F 

(70-95°C)

,  refrigerant  vapor 

can be liberated in a usable quantity.  If a 
mixing valve is to be used to control this 
temperature, 

IT 

MUST 

NOT 

BE 

COMBINED  WITH  THE  HEAT  MEDIUM 
BYPASS  VALVE.    It  MUST  be  a 
separate and distinct control. 

The key device required for the proper 

operation  of  the  unit  is  a  Heat  Medium 
Bypass  Valve.    When  the  unit  requires 
heat medium,  it will send a signal to this 
valve  to  open.    When  the  unit  does  not 
require  heat  medium,  for  whatever 
reason,  this  valve  will  be  commanded  to 
move into bypass position. 

Содержание AROACE

Страница 1: ...hot water from a process cogeneration solar or other waste heat source capable of providing a temperature range of 158 203 F 70 95 C CONTENTS GENERAL Page GENERAL 2 MODEL DESIGNATION 2 STANDARD SPECI...

Страница 2: ...check the installation and supervise or conduct the initial startup and operation of the unit CAUTION THE YAZAKI WARRANTY WILL BE VOIDED IF THE FOLLOWING RESTRICTIONS ARE NOT OBSERVED 1 DO NOT OPEN AN...

Страница 3: ...liters 9 8 37 Heat Medium Heat Input Mbtu hr kW hr 85 7 25 1 Temperature Inlet F C 190 4 88 Outlet F C 181 4 83 Range F C 158 203 70 95 Generator Pressure Loss PSI kPa 11 2 77 0 Maximum Operating Pre...

Страница 4: ...4 EQUIPMENT DIMENSIONS Figure 1 Equipment Dimensions...

Страница 5: ...5 INTERNAL WIRING DIAGRAM Figure 2 Internal Wiring Diagram...

Страница 6: ...AUX2 is closed Not Used P1 Chilled Water Pump ON signal Supplied by the chiller P1D Chilled Water Pump Operation Input Pump overloads P2 Cooling Water Pump ON signal Supplied by the chiller P2D Coolin...

Страница 7: ...al configuration THERE IS NO ALTERNATIVE Transport by vehicle over roadway while the unit is not in the vertical configuration will void the warranty 2 The unit may ONLY lay over onto its back the sid...

Страница 8: ...the horizontal configuration let it gently rest on the blocks that were attached during step 2 8 Once the unit is to be turned back to the vertical configuration it is preferable that the unit again b...

Страница 9: ...make certain the concrete base and the soil beneath are sufficient for the task Settling over time could cause the unit to become unlevel which could have a negative impact on the performance and lif...

Страница 10: ...ach fluid circuit connection to facilitate startup future service and routine maintenance Strainers in each circuit particularly the cooling water circuit are recommended as well These should be place...

Страница 11: ...installed between the machine and the balance stop valves so as to allow for flushing of the absorber condenser coils should it ever become necessary CAUTION 1 DO NOT EXCEED 100 120 OF STANDARD COOLI...

Страница 12: ...thod in the USA is the use of glycol in the fluid loop Glycol may be permitted for use in Yazaki chiller with certain restrictions and observations 1 Do not use automotive glycol Antifreeze since it c...

Страница 13: ...e are two power supply boards in the Control Box that will take voltage within this range and supply proper output voltage One power supply generates 24vdc to power the Solution Pump and provide 24 vo...

Страница 14: ...s CaCO3 ppm 50 150 50 50 Ionic silica SiO2 ppm 30 50 30 30 Reference Total iron Fe ppm 1 0 1 0 1 0 0 3 Copper Cu ppm 1 0 0 3 1 0 0 1 Sulfide ion S 2 ppm ND ND ND ND Ammonium ion NH4 ppm 1 0 1 0 0 1 0...

Страница 15: ...tank properly charged installed on heat medium piping 13 Water make up and fill lines installed to the cooling tower 14 Pressure relief valves set to maximum of 85 3 psig 588 kPa installed on piping...

Страница 16: ...EMS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web www yazakienergy com This symbol on the product s nameplate means it is...

Отзывы: