u
Three-Phase 200 V Class Drive Models 2A0114 to 2A0396
Table A.2 Power Ratings Continued (Three-Phase 200 V Class)
Item
Specification
CIMR-Z
o
2A
0114
0143
0169
0211
0273
0343
0396
Maximum
Applicable
Motor
Capacity
HP
40
50
60
75
100
125
150
kW
30
37
45
55
75
90
110
Input
Input Current (A)
114
143
169
211
273
343
396
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Minimum Power Supply Capacity (kVA)
48
60
71
88
114
143
165
Output
Rated Output Capacity (kVA)
45
57
67
84
109
137
158
Rated Output Current (A)
143
273
Overload Tolerance
110% of rated output current for 60 s
140% of rated output current for 0.5 s
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Maximum Output Frequency (Hz)
240 Hz
Harmonics
Reduction
DC Link Choke
Built-in
EMC
Filter (IEC/EN 61800-3 Category 2)
Built-in
External
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 230 V.
<4> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
<5> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
269
A
Specifications