C.4 BACnet Setup Parameters
u
BACnet Serial Communication
This section describes parameters necessary to set up BACnet communications.
n
H5-01: Drive Slave Address
Sets the drive slave address used for communications.
Note:
Cycle power for the setting to take effect.
No.
Name
Setting Range
Default
H5-01
Drive Slave Address
0 to FFH
1FH
Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to
be assigned in sequential order, but no two drives may share the same address.
n
H5-02: Communication Speed Selection
Sets the communications speed for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2.
Note:
1.
Cycle power for the setting to take effect.
2.
When Metasys N2 communications are selected (H5-08 = 1), selecting a baud rate other than 9600 bps will trigger an oPE29 error.
3.
When APOGEE FLN (P1) communications are selected (H5-08 = 2), selecting a baud rate other than 4800 bps will trigger an oPE29
error.
4.
When BACnet communications are selected (H5-08 = 3), selecting 115200 bps (Setting 8) will trigger an oPE29 error.
No.
Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 8
<1> Default depends on H5-08 setting:
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
38400 bps
1
2400 bps
57600 bps
2
4800 bps
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
<1> Not available when H5-08 is set to 2 P1 (APOGEE FLN).
<2> Not available when H5-08 is set to 0 (MEMOBUS/Modbus) or 1 (Metasys N2).
n
H5-03: Communication Parity Selection
Sets the parity used for communications.
Note:
Cycle power for the setting to take effect.
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
n
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
C.4 BACnet Setup Parameters
346
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual