APPENDIX 3 TYPICAL CONNECTION DIAGRAM
71
APPENDIX 3 TYPICAL CONNECTION DIAGRAM
3.1
BRAKING RESISTOR UNIT
For Models CIMR
−
G5C51P5 to
−
G5C5015 (575 V Class 1.5 to 15 kW)
1
2
©
¨
1
DC Reactor
(Option) *
Braking Resistor Unit
[
VS
−
616G5
3
−
Phase
Power Supply
500 to 600 V
50/60 Hz
L1
L1 (R)
L2
L2 (S)
L3
L3 (T)
THRX OFF
ON
MC
SA
Overload Relay Trip Contact
of Braking Resistor Unit
1
2
MC
TRX
TRX
20 18
Fault
Contact
Forward Run/Stop
Reverse Run/Stop
Factory
Setting
External Fault
Fault Reset
Multi
−
step Speed Setting 1
(Master/Aux Change)
Multi
−
step Speed
Setting 2
Jog Reference
External Baseblock
Use sequencer to break
power supply side on
overload relay trip contact
of braking resistor unit.
¨
2
B1
B2
SA
SA
THRX
2 k
Ω
2 k
Ω
0 to +10 V
4 to 20 mA
P
0 to +10 V
P
0 V
P
Master
Frequency
Reference
Multi
−
function
Open Collector
Output
48 V 50 mA or
less
27
Opto
−
coupler Output 2
(Speed Agree Signal at
Factory Setting)
26
Opto
−
coupler output 1
(Zero Speed Signal at
Factory Setting)
25
Multi
−
function Contact Output
250 VAC 1 A or less
30 VDC 1A or less
(Signal during Running at Factory
Setting)
10
9
20
19
Fault Contact Output
250 VAC 1 A or less
30 VDC 1 A or less
18
20
+
AM
23
+
−
Multi
−
function Analog Output
−
10 to +10V 2 mA
(Output Current at Factory
Setting)
21
22
FM
−
Analog
Monitor 1
E
Multi
−
function Analog Output
−
10 to +10 V 2 mA
(Output Frequency at Factory
Setting)
U (T1)
V (T2)
W (T3)
Motor
IM
1 Forward Run when
CLOSED
2 Reverse Run when
CLOSED
3
4
5
6
7
8
Multi
−
function
Contact Input
11
E
15 Freq. Setting Power
15V 20 mA
13 Master Freq. Ref.
0 to 10V (20k
Ω
)
14 Master Freq. Ref.
4 to 20 mA (250
Ω
)
16 Multi
−
function Analog Input
0 to 10V (20k
Ω
)
0 V
33 Freq. Setting Power Supply
−
15V 20 mA
17 (Aux Freq. Ref. at
Factory Setting)
MC
Analog
Monitor 2
18
* When installing a DC reactor (option), remove the common bar between
¨
1 and
¨
2 terminals
(provided as standard) and connect a DC reactor with the terminals.
[
When using the braking resistor unit, set constant L3
−
04 to “0” (stall prevention selection during
decel is disabled). If it is not changed, the inverter may not stop within set decel time.
Short
−
circuit
Bar
Line Filter
37
Shield Sheath
Connection Terminal
+24V
35
36
250 VAC or less
Fuse
MC
Overload Relay Trip Contact
B
P
x