52
(1)
Changing Control Method
( Example )
The control method is changed from open loop vector to V/f control.
Table 21 Changing Control Method
Description
Key Sequence
Digital Operator Display
Remarks
⋅
Displaying frequency reference.
⋅
Displays Operation.
⋅
Displays Initialize.
⋅
Select Initialize.
⋅
Change the constant name.
(Displays Control Method.)
⋅
By depressing DATA/ENTER key, constant
No. and set value are displayed.
⋅
Change the control method.
(Displays V/F Control.)
⋅
Select V/F Control.
⋅
Return to Operation.
⋅
Select Operation to display frequency
reference.
DATA
ENTER
MENU
DATA
ENTER
DATA
ENTER
DATA
ENTER
MENU
Frequency Ref
U1
−
01 = 60.00 HZ
** Main Menu **
Operation
** Main Menu **
Initialize
Select Language
English
Control Method
Open Loop Vector
A1
−
02 = 02 ***
Open Loop Vector
A1
−
02 = 00
V/F Control
Entry Accepted
** Main Menu **
Operation
Frequency Ref
U1
−
01 = 60.00 HZ
When selecting Initialize, Select
Language is displayed.
After displaying Entry Accepted
for 1.5 seconds, returns to the
control method display.