5
SETTING OPERATION CONDITIONS
57
5.6
MODIFIED CONSTANTS MODE
Compares the constant values preset at the factory with the values changed by the user, and displays
the constants changed from the preset constants automatically. In the modified constants mode,
constants can be read; in addition, they can also be set or changed.
( Example )
Read the constants C1
−
01 (accel time 1) and E1
−
01 (input voltage) when the factory settings
have been changed. In addition, change the setting of E1
−
01 (input voltage) from 575V to
600V in this mode.
Table 26 Typical Operation in Modified Constants Mode
Description
Key Sequence
Digital Operator Display
Remarks
⋅
Displaying frequency reference.
⋅
Displays Operation.
⋅
Displays Modified Consts.
⋅
Select the Modified Consts.
⋅
Displays the next
−
to
−
be
−
changed constant.
(Displays input voltage.)
⋅
Depress DATA/ENTER key.
The value to be set blinks.
⋅
Change the value to 600V.
⋅
Write
−
in the constant.
⋅
Displays the next
−
to
−
be
−
changed constant.
⋅
Returns to Main Menu.
(Displays Operation.)
⋅
Select Operation to display frequency
reference.
DATA
ENTER
MENU
DATA
ENTER
DATA
ENTER
DATA
ENTER
MENU
RESET
Frequency Ref
U1
−
01 = 60.00 HZ
** Main Menu **
Operation
** Main Menu **
Modified Consts
Accel Time 1
C1
−
01 =
20.0 Sec
Input Voltage
E1
−
01 =
575 VAC
Input Voltage
575 VAC
Input Voltage
600 VAC
Entry Accepted
Accel Time 1
C1
−
01 =
20.0 Sec
** Main Menu **
Operation
Frequency Ref
U1
−
01 = 60.00 HZ
When selecting Modified Consts
the constants which have been
changed from factory settings are
displayed.
After displaying Entry Accepted
for 1.5 seconds, returns to input
voltage display.