The parameterization defines if the gate interrupts or aborts the counter process.
n
At
abort function
the counter starts counting with the
load value
after gate restart.
n
At
interrupt function
, the counter starts counting with the recent
counter value
after
gate restart.
The
compare value
is to be pre-defined by the
output area
. The
comparison bit
may be
found at the
counter status
at STS_COMP. Please consider that the bit STS_COMP may
only be influenced when in the counter status the bit STS_CTRL_COMP is set. The fol-
lowing behavior for the
comparison bit
may be pre-defined via the parameterization:
n
no comparison:
Comparison bit
is not influenced
n
Counter value
³
comparison value
:
Comparison bit
is set
n
Counter value
£
comparison value
:
Comparison bit
is set
n
Counter value
=
comparison value
:
Comparison bit
is set
no comparison
The
comparison bit
is not influenced.
Comparison bit is set when counter value
³
comparison value
Comparison function
VIPA System SLIO
Deployment
Counter additional functions
HB300 | FM | 050-1BB00 | en | 19-38
53