3.3 Technical data
Order no.
050-1BB00
Type
FM 050
Module ID
08C3 380A
Current consumption/power loss
Current consumption from backplane bus
75 mA
Power loss
0.9 W
Technical data digital inputs
Number of inputs
4
Cable length, shielded
100 m
Cable length, unshielded
-
Rated load voltage
DC 20.4...28.8 V
Reverse polarity protection of rated load voltage
-
Current consumption from load voltage L+ (without load)
15 mA
Rated value
DC 20.4...28.8 V
Input voltage for signal "0"
DC 0...5 V
Input voltage for signal "1"
DC 15...28.8 V
Input voltage hysteresis
-
Signal logic input
-
Frequency range
-
Input resistance
-
Input current for signal "1"
3 mA
Connection of Two-Wire-BEROs possible
ü
Max. permissible BERO quiescent current
0.5 mA
Input delay of "0" to "1"
0.8 µs
Input delay of "1" to "0"
0.8 µs
Number of simultaneously utilizable inputs horizontal con-
figuration
4
Number of simultaneously utilizable inputs vertical configu-
ration
4
Input characteristic curve
IEC 61131-2, type 1
Initial data size
12 Byte
Technical data digital outputs
Number of outputs
-
Cable length, shielded
-
Cable length, unshielded
-
Rated load voltage
-
Current consumption from load voltage L+ (without load)
-
VIPA System SLIO
Hardware description
Technical data
HB300 | FM | 050-1BB00 | en | 19-38