![YASKAWA VIPA SLIO FM 050-1BB00 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/yaskawa/vipa-slio-fm-050-1bb00/vipa-slio-fm-050-1bb00_manual_3311975043.webp)
4.2.2 Output area 12byte
At CPU, PROFIBUS and PROFINET the output area is embedded to the corresponding
address area.
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 7000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
CV_I
4
Counter 0:
Comp. value
5600h/s
01h
+4
CV_II
4
Counter 1:
Comp. value
5600h/s+1
02h
+8
CSTS_I
2
Counter 0:
Control word
5602h/s
03h
+10
CSTS_II
2
Counter 1:
Control word
5602h/s+1
04h
With
comparison value
a value may be preset that may influence the
comparison bit
res.
throw a process interrupt when compared with the recent counter value. The behavior of
the
comparison bit
STS_COMP in the
counter status
res. the process interrupt has to be
set for counter 0 via the parameter INT_I and INT_II for counter 1.
Bit
Name
Function
0
-
reserved
1
CTRL_COMP_SET
enables the
comparison bit
2
SW_GATE_SET
sets the software gate
3 ... 4
-
reserved
5
COUNTERVAL_SET
sets counter temporarily
to the value of
set value
6
RES_SET
resets the bits
STS_CMP, STS_END,
STS_OFLW, STS_UFLW
and STS_ZP with edge 0-1
7 ... 8
-
reserved
9
CTRL_COMP_RESET
disables the
comparison bit
10
SW_GATE_RESET
resets the software gate
11 ...
15
-
reserved
Output area
CC_I CC_II Comparison
value
CCTRL_I CCTRL_II Con-
trol word
VIPA System SLIO
Deployment
In-/Output area > Output area 12byte
HB300 | FM | 050-1BB00 | en | 19-38
43