![YASKAWA VIPA SLIO FM 050-1BB00 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/yaskawa/vipa-slio-fm-050-1bb00/vipa-slio-fm-050-1bb00_manual_3311975045.webp)
Name
Bytes
Function
Default
DS
IX
SX
HYST_II
1
C1: Hysteresis
00h
83h
3127h
16h
CRES
1
reserved
00h
83h
3128h
17h
*) This parameter may only be transferred at STOP state.
Byte
Bit 7...0
0
Diagnostic interrupt
n
00h = disable
n
40h = enable
n
Here you activate res. de-activate the diagnostic function.
Byte
Function
Possible values
0
Input frequency C0 track A
n
02h: 100kHz
n
03h: 60kHz
n
04h: 30kHz
n
06h: 10kHz
n
07h: 5kHz
n
08h: 2kHz
n
09h: 1kHz
Other values are not permis-
sible!
1
Input frequency C0 track B
2
Input frequency C1 track A
3
Input frequency C1 track B
n
Input frequency
allows you to preset a filter for I1, I4, I5 and I8. With the help of filters
you may e.g. filter signal peaks at a blurred input signal.
Byte
Bit 7 ... 0
0
Bit 5 ... 0: Interrupt behavior
n
Bit 0: 0 (fix)
n
Bit 1: 0 (fix)
n
Bit 2: Proc. interrupt overflow
n
Bit 3: Proc. interrupt underflow
n
Bit 4: Proc. interrupt
comparison value
n
Bit 5: Proc. interrupt
end value
n
Bit 7 ... 6
: 0 (fix)
n
Setting the appropriate bit activates the associated process interrupt
DIAG_EN Diagnostic inter-
rupt
CHxx Input frequency
INT_I/II, C0/C1: Interrupt
behavior
VIPA System SLIO
Deployment
Parameter data
HB300 | FM | 050-1BB00 | en | 19-38
45