Chapter 2 Hardware description
Manual VIPA System 300S
2-6
HB140E - IM - RE_353-1DP01 - Rev. 14/47
Technical data
Order no.
353-1DP01
Type IM
353DP
SPEED-Bus -
Technical data power supply
Power supply (rated value)
DC 24 V
Power supply (permitted range)
DC 20.4...28.8 V
Reverse polarity protection
9
Current consumption (no-load operation)
70 mA
Current consumption (rated value)
1 A
Inrush current
60 A
I²t 0.45
A²s
Max. current drain at backplane bus
3.5 A
Max. current drain load supply
-
Power loss
2.5 W
Status information, alarms, diagnostics
Status display
yes
Interrupts yes,
parameterizable
Process alarm
yes, parameterizable
Diagnostic interrupt
yes, parameterizable
Diagnostic functions
yes, parameterizable
Diagnostics information read-out
possible
Supply voltage display
green LED
Service Indicator
-
Group error display
red LED
Channel error display
none
Hardware configuration
Racks, max.
1
Modules per rack, max.
29
Number of digital modules, max.
29
Number of analog modules, max.
16
Communication
Fieldbus
PROFIBUS-DP to EN 50170
Type of interface
RS485
Connector
Sub-D, 9-pin, female
Topology
Linear bus with bus termination
at both ends
Electrically isolated
9
Number of participants, max.
125
Node addresses
1 - 99
Transmission speed, min.
9.6 kbit/s
Transmission speed, max.
12 Mbit/s
Address range inputs, max.
244 Byte
Address range outputs, max.
244 Byte
Number of TxPDOs, max.
-
Number of RxPDOs, max.
-
Housing
Material PPE
Mounting
Rail System 300
Mechanical data
Dimensions (WxHxD)
40 x 125 x 120 mm
Weight 170
g
Environmental conditions
Operating temperature
0 °C to 60 °C
Storage temperature
-25 °C to 70 °C
Certifications
UL certification
Yes
KC certification
Yes