Manual VIPA System 300S
Chapter 2 Hardware description
HB140E - IM - RE_353-1DP01 - Rev. 14/47
2-5
The PROFIBUS slave has an internal power supply. This power supply
requires DC 24V. In addition to the electronics on the bus coupler, the
supply voltage is also used to power any modules connected to the
backplane bus. Please note that the maximum current that the integrated
power supply can deliver to the backplane bus is 3.5A.
The power supply is protected against reverse polarity.
PROFIBUS and backplane bus are galvanically isolated from each other.
Attention!
Please ensure that the polarity is correct when connecting the power
supply!
Via a 9pin RS485 interface, you connect the PROFIBUS slave with your
PROFIBUS network.
The pin assignment of this interface is as follows:
Pin
Assignment
Bus termination
1 n.c
2 n.c.
3
RxD/TxD-P (Line B)
4 RTS
5 M5V
6 P5V
7 n.c.
8
RxD/TxD-N (Line A)
9 n.c.
3
8
P5V
M5V
330
330
220
RxD/TxD-P(B)
RxD/TxD-N(A)
5
6
RxD/TxD-P(B)
RxD/TxD-N(A)
Note!
The PROFIBUS line has to be terminated with its ripple resistor. Please
make sure to terminate the last participants on the bus at both ends by
activating the terminating resistor.
Power supply
RS485 interface