Chapter 3 Deployment
Manual VIPA System 300S
3-20
HB140E - IM - RE_353-1DP01 - Rev. 14/47
Note!
To connect this EasyConn plug, please use the standard PROFIBUS cable
type A (EN50170). Starting with release 5 you also can use highly flexible
bus cable: Lapp Kabel order no.: 2170222, 2170822, 2170322.
With the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating tool
that makes the connection of the EasyConn much easier.
11
6
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to
activate a terminating resistor.
1./last
bus participant
further
participants
Attention!
The terminating resistor is only
effective, if the connector is installed at
a bus participant and the bus participant
is connected to a power supply.
Note!
A complete description of installation
and deployment of the terminating
resistors is delivered with the connector.
•
Loosen the screw.
•
Lift contact-cover.
•
Insert both wires into the ducts
provided (watch for the correct
line color as below!)
•
Please take care not to cause a
short circuit between screen and
data lines!
•
Close the contact cover.
•
Tighten screw
(max. tightening torque 4Nm).
The
green
line must be connected to
A
, the
red
line to
B
!
Termination with
"EasyConn"
Wiring
Assembly