Chapter 3 Deployment
Manual VIPA System 300S
3-12
HB140E - IM - RE_353-1DP01 - Rev. 14/47
Note
Please note to place the following modules during hardware configuration
to the first three slots:
Config
for
Slot1
Config
for
Slot2
Config
for
Slot3
These modules are automatically placed using the Siemens SIMATIC
Manager:
At usage of the IM 353-1DP01 (DP-V0) you have the following parameter
data:
Byte
Bit 7 ... Bit 0
Default
0
Bit 2 ... 0: 0 (fix)
Bit 3: 0 = WD-Timebase 10ms
1 = WD-Timebase 1ms
Bit 4: 0 (fix)
Bit 5: 0 = Publisher-Mode not available
1 = Publisher-Mode available
00h
1)
1 00h
(fix)
00h
2 08h
(fix)
08h
3 0Ah
(fix)
0Ah
4 81h
(fix)
81h
5 00h
(fix)
00h
6 00h
(fix)
00h
7
Bit 0: 0 = Identifier-related diagnostic enable
1 = Identifier-related diagnostic disable
Bit 1: 0 = Module status enable
1 = Module status disable
Bit 2: 0 = Channel-related diagnostic enable
1 = Channel-related diagnostic disable
Bit 3: 0 (fix)
bit 4: 0 (fix)
Bit 5: 0 = V0: Diagnostic interrupt not available
1 = V0: Diagnostic interrupt available
Bit 6: 0 = V0: Hardware interrupt not available
1 = V0: Hardware interrupt available
Bit 7: 0 (fix)
70h
8
Bit 7 ... 0: 0 (fix)
00h
9 ... 12 00h (fix)
00h
1)
Using the Siemens SIMATIC Manager this value is automatically set and can not be
changed.
Parameter data
IM 353-1DP01