B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
343
Pa
ra
met
er
Li
st
B
Note:
Cycle power to the drive to enable MEMOBUS/Modbus settings.
◆
L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, torque limits and other types of hardware protection.
H6-04
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is
input.
-100.0 to
+100.0
0.0% A A A
42F
H6-05
Pulse Train Input Filter
Time
Sets the pulse train input filter time constant.
0.00 to
2.00
0.10 s A A A
430
H6-06
Pulse Train Monitor
Selection
Select the pulse train monitor output function (value of the
-
part of U
-
).
Refer to U: Operation Status Monitors on page 358
for
the list of U monitors.
Example: To select U5-01, set “501. ”When not using this
parameter or when using in the through mode, set “000”.
000, 031,
101, 102,
105, 116,
501, 502
102
A A A
431
H6-07
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the
monitor value is 100%. Set H6-06 to “102” and H6-07 to
“0”, to make the pulse train monitor output equal to the
output frequency.
0 to 32000
1440
Hz
A A A
432
H6-08
Pulse Train Input Minimum
Frequency
Sets the minimum frequency for the pulse train input to be
detected. Enabled when H6-01 = 0, 1, or 2.
0.1 to
1000.0
0.5
Hz
A A A
43F
<15> Parameter can be changed during run.
<25> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<26> The availability of certain functions depends on the control method used.
<36> Default setting is determined by the initialize mode the drive is set for (o2-09).
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
L1: Motor Protection
Use L1 parameters to configure motor protective functions.
L1-01
Motor Overload Protection
Selection
Sets the motor thermal overload protection (oL1) based on
the cooling capacity of the motor.
0: Disabled
1: Standard Fan Cooled (speed range < 10:1)
2: Standard Blower Cooled (speed range
≥
10:1)
3: Vector Motor (speed range 100:1)
4: PM motor with variable torque
NOTICE:
When using a single drive to operate multiple
motors, set L1-01 to 0 and ensure each motor has a thermal
relay installed.
0 to 4
1
S S S
480
L1-02
Motor Overload Protection
Time
Sets the motor thermal overload protection (oL1) time.
A larger L1-02 time will increase the time for an oL1 fault
to occur.
This parameter does not typically require adjustment.
Should be set in accordance with the overload tolerance of
the motor.
0.1 to 5.0
1.0
min
A A A
481
L1-03
Motor Overheat Alarm
Operation Selection (PTC
input)
Sets operation when the motor temperature analog input
(H3-02 and H3-10 = E) exceeds the oH3 alarm level (PTC
input level: Tr-5
°
C).
0: Ramp to Stop
1: Coast to Stop
2: Fast-stop using C1-09
3: Alarm Only (“oH3” will flash)
0 to 3
3
A A A
482
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...