B.3 Parameter Table
358
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
◆
U: Operation Status Monitors
Monitor parameters allow the user to view drive status, fault information, and other information about drive operation.
T1-07
Motor Rated Speed
Sets the base speed of the motor in revolutions per minute r/min
(RPM).
0 to 24000
1450
r/min
A A
−
707
T1-11
Motor Iron Loss
Provides the iron loss for determining the Energy Saving
coefficient.
The value set to E2-10 (motor iron loss) when the power is
cycled. If T1-02 is changed, an initial value valid for the
selected capacity will be shown.
0 to 65535
14 W
A
− −
70B
These values differ depending on
the motor code value and motor
parameter settings.
<17> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<31> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control, and 2 for Motor 2 control.
<33> Default setting is determined by the drive model selection set in parameter o2-04 and C6-01, Drive Duty Selection.
No.
Name
Description
Analog Output
Level
Unit
Control
Mode
Addr.
Hex
V/f OL
V
P
M
U1: Operation Status Monitors
Use U1 monitors to display the operation status of the drive.
U1-01
Frequency Reference
Monitors the frequency
10 V: Max
frequency
0.01
Hz
A A A
40
U1-02
Output Frequency
Displays the output frequency. Display units are
determined by o1-03.
10 V: Max
frequency
0.01
Hz
A A A
41
U1-03
Output Current
Displays the output current.
10 V: Drive rated
current
A A A
42
U1-04
Control Method
Control method set in A1-02.
0: V/f without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
No output signal
available
–
A A A
43
U1-05
Motor Speed
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Maximum
speed
0.01
Hz
A A –
44
U1-06
Output Voltage Reference
Displays the output voltage.
10 V: 200 Vrms
(400 Vrms)
0.1 V A A A
45
U1-07
DC Bus Voltage
Displays the DC bus voltage.
10 V: 400 V (800
V)
1 V
A A A
46
U1-08
Output Power
Displays the output voltage (this value is determined
internally).
10 V: Drive
capacity (kW)
(rated motor
capacity)
A A A
47
U1-09
Torque Reference
Monitor of internal torque reference value for Open Loop
Vector (OLV) control
10 V: Motor rated
torque
0.1% – A –
48
U1-10
Input Terminal Status
Displays the input terminal status.
No output signal
available
–
A A A
49
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
Digital input terminal
S1 enabled
Digital input terminal
S2 enabled
Digital input terminal
S3 enabled
Digital input terminal
S4 enabled
Digital input terminal
S5 enabled
Digital input terminal
S6 enabled
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...