5.8 L: Protection Functions
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
187
P
a
ra
me
te
r D
eta
ils
5
■
L1-02: Motor Overload Protection Time
Sets the time it takes the drive to detect motor overheat due to overload. This setting rarely requires adjustment, but
should correlate with the motor overload tolerance protection time for performing a hot start.
• Defaulted to operate with an allowance of 150% overload operation for one minute.
•
shows an example of the electrothermal protection operation time using a general-purpose motor
operating at 60 Hz with L1-02 set to one minute.
Figure 5.65
Figure 5.65 Motor Protection Operation Time
■
Motor Protection Using a Positive Temperature Coefficient (PTC)
A motor PTC can be connected to an analog input of the drive. This input is used by the drive for motor overheat
protection.
When the motor overheat alarm level is reached, an oH3 alarm will be triggered and the drive will continue operation as
selected in L1-03. When the overheat fault level is reached, an oH4 fault will be triggered, a fault signal will be output,
and the drive will stop the motor using the stop method determined in L1-04.
Connect the PTC between terminals AC and A1 and set jumper S4 on the terminal board to “PTC” like shown in
. Set parameter H3-01 to 0 and parameter H3-02 to E.
Figure 5.66
Figure 5.66 Connection of a Motor PTC
No.
Name
Setting Range
Default
L1-02
Motor Overload Protection Time
0.1 to 5.0 min
1.0 min
Operation time (minutes)
Cold start
Hot start
Motor current (%)
E2-01 = 100% m o t o r c u r r e n t
10
7
3
1
0.4
0.1
0
100
150
200
C1
Drive
Multi-function input
PTC
thermistor
MA
Multi-function
output (contact)
Multi-function
output (photocoupler)
MB
MC
P2
P1
C2
A1 (0-10 V)
AC
PTC
AI
DIP Switch S4
V
I
DIP switch S1
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...