Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
9 of 30
Reactive Power Control
6
The feature allows inverter to stabilize the grid by compensating the reactive power. The image below shows
the default setting of Reactive Power Control. The default state of this feature is deactivated.
Example:
If the cutomer wants to enable this feature and set the inverter to run at 60% of maximum reactive power
capability. The procedure via the web-based GUI is shown below.
Write “ -60 ” to Constant Var
Click the little box on the top left corner of the configuration window to enable Reactive Power Control
Click Save button to apply the settings to local inverter
The alternative method is to use software which supports Modbus TCP/IP. The register address is shown
below.