Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
8 of 30
Write “ +0.8 ” to Power Factor
Click the little box on the top left corner of the configuration window to enable Power Factor
Click Save button to apply the setting to local inverter
The alternative method is to use software which supports Modbus TCP/IP. The register address is shown
below.
To implement the same setting, the procedure is shown below.
Write “ 80 “ to register 40300
Write “ 1 “ to register 40304