![YASKAWA SOLECTRIA XGI 1500 Series Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/yaskawa/solectria-xgi-1500-series/solectria-xgi-1500-series_manual_3637410024.webp)
Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
24 of 30
Write “ 62.0 ” to HF2 Freq Threshold
Write “ 0.16 ” to HF2 Disconnect Time
Write “ 60.5 ” to HF1 Freq Threshold
Write “ 300.00 ” to HF1 Disconnect Time
Write “ 58.5 ” to LF1 Freq Threshold
Write “ 300.00 ” to LF1 Disconnect Time
Write “ 57.00 ” to LF2 Freq Threshold
Write “ 0.16 ” to LF2 Disconnect Time
Click Save button to apply the settings to local inverter
The alternative method is to use software which supports Modbus TCP/IP. The register address is shown
below.